Sontay SC-IO-24 Mode D'emploi page 10

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Output Overwrite Status
Indicates that the output is overridden by the
25
40026
hardware switch (SW5-SW10).
Universal Input 1 Function
26
40027
Universal Input 2 Function
27
40028
Universal Input 3 Function
28
40029
Universal Input 4 Function
29
40030
Universal Input 5 Function
30
40031
Universal Input 6 Function
31
40032
Universal Input 7 Function
32
40033
Universal Input 8 Function
33
40034
Universal Input 1 Offset
34
40035
Universal Input 2 Offset
35
40036
Universal Input 3 Offset
36
40037
Universal Input 4 Offset
37
40038
Universal Input 5 Offset
38
40039
Universal Input 6 Offset
39
40040
Universal Input 7 Offset
40
40041
Universal Input 8 Offset
41
40042
Analogue Output 1 Mode
42
40043
Analogue Output 1 Minimum Voltage
43
40044
Analogue Output 1 Maximum Voltage
44
40045
mode d'emploi
Bit String
[B0..B10]
Unsigned
[1..4]
Signed
[0..100]
Scale 100
Unsigned
[1..4]
Signed
[0..100]
Scale 10
Téléphone:
+33 (0)1 46 94 62 92 -
E-mail:
© 2012-2015 Sontay Limited. Tous droits réservés
SC-IO-24~-Mode d'emploi
Date of Issue: 02/11/2015
Issue Number: 5.0
Page 10 of 11
B0 = Relay 1
B1 = Relay 2
B2 = Relay 3
B3 = Relay 4
B4 = Relay 5
B5 = Relay 6
B6 = AO1
B7 = AO2
B8 = AO3
B9 = AO4
1 = Temperature °C
2 = Temperature °F
3 = 0-10V
4 = Digital Input
5 = 0-5V
6 = 4-20mA
Range: +/- 5,00, Resolution : 0,10
1 = Analogue
2 = On/Off
3 = Pulse
4 = 4-20mA
Unit: Volt, Range: 0 V - Register 44,
Unit: Volt, Range: Register 43 - 10.0V,
Service.Clients@sontay.fr. -
Internet:
W
W
W
Resolution : 0,1
W
Resolution : 0,1
www.sontay.fr
0000,
0000,
0000, 0000b
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
0
100

Publicité