L8148A,E,J
Aquastat® Relays
APPLICATION
The L8148A,E,J Aquastat
controllers for use with forced hydronic heating
systems. The combination high limit and intermediate
switching relay works with a low voltage (24V)
thermostat to control burner and circulator circuits. A
call for heat by the thermostat starts both the burner
and the circulator. When boiler-water temperature
exceeds the high-limit settings, the burner circuit is
broken; the circulator continues to operate during the
thermostat call for heat.
The L8148A controls line-voltage burner circuits; the
L8148E,J control low-voltage burner circuits; the
L8148J controls millivoltage burner circuits. All models
control line-voltage circulator circuits.
L8148A,E,J have provisions for adding low-limit
controllers; L8148E,J can power valves in multizone
systems.
L8148E is available with a plug and 50 VA transformer
for use with Resideo Smart Valve SV9500/SV9600.
SPECIFICATIONS
Electrical Ratings:
Table 1. Circulator Control Circuit (A):
Type
Full Load
7.4
Locked Rotor
44.4
Table 2. Burner Control Circuit:
Model No.
Voltage
L8148A
Line
L8148E,J
Low
Scale Range: 140°F to 240°F (60°C to 116°C) or 180°F to
240°F (82°C to 116°C).
Differential: Nonadjustable.
High Limit Dial Stop: Adjustable.
®
Relays are immersion-type
120 Vac
240 Vac
3.7
22.7
Electrical Rating
Same as circulator control
circuit.
0.8A maximum at 24 Vac.
INSTALLATION INSTRUCTIONS
Maximum Pressure on Immersion Well: 255 psi
(1758 kPa).
Maximum Ambient Temperature: 150°F (66°C) with
1.2A, 24V load; 77°F (25°C) with 1.4A, 24V load.
Maximum Bulb Temperature: 40°F over setpoint, up to
265°F (4°C over setpoint, up to 129°C).
Thermostat Heat Anticipator Setting: 0.2A.
Material Safety Data Sheets (MSDS): For information on
heat-conductive compound, see form number
69-0955.
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable
for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Explosion Hazard.
Can cause severe injury, death or property
damage.
This product is intended for use only in systems
with a pressure relief valve.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
1. Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
2. Never apply a jumper across (or short)
terminals B1, B2, or B3. This burns out the
transformer.
95-6940EF-01

Publicité

loading

Sommaire des Matières pour resideo Aquastat L8148A

  • Page 1 L8148E is available with a plug and 50 VA transformer 2. Check the ratings given in the instructions and on for use with Resideo Smart Valve SV9500/SV9600. the product to make sure the product is suitable for your application.
  • Page 2 L8148A,E,J AQUASTAT® RELAYS Mounting 7. Fit the case into the well so the clamp on the case slides over the flange on the well. The L8148A,J has a case that can be converted to either IMPORTANT horizontal or vertical mounting (Fig. 1). Best thermal response is obtained with a well that snugly fits the sensing bulb.
  • Page 3 L8148A,E,J AQUASTAT® RELAYS BACK OF IMMERSION CONTROLLER WELL CLAMP CONTROLLER CASE BOILER CASE IMMERSION WELL CLAMP IMMERSION ADAPTER WELL SPUD IMMERSION ADAPTER WELL CLAMP OLD IMMERSION SENSING SCREW WELL ASSEMBLY BULB HEAT-CONDUCTIVE COMPOUND BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD CAPILLARY THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).
  • Page 4 L8148A,E,J AQUASTAT® RELAYS THERMOSTAT L8148A HIGH LIMIT L6006 LOW LIMIT CONTROLLER TO LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE CIRCULATOR JUMPER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOADPROTECTION AS REQUIRED. REMOVE JUMPER WHEN ADDING L6006 LOW LIMIT CONTROLLER. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
  • Page 5 L8148A,E,J AQUASTAT® RELAYS T87F T87F T87F R845 R845 R845 RELAY PUMP PUMP PUMP (HOT) L8148A ORANGE WHITE C554 BLACK BURNER IGNITION R8184G POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. M2843A B1 IS 1/4 IN.
  • Page 6 L8148A,E,J AQUASTAT® RELAYS ZONE 2 ZONE 1 ZONE 3 24 VOLT 24 VOLT 24 VOLT V8043F THERMOSTAT THERMOSTAT THERMOSTAT END SWITCH V8043F V8043F END SWITCH END SWITCH L8148J MILLIVOLTAGE POWERPILE ® GAS VALVE LOW VOLTAGE GAS VALVE (eg, VR8300) THTR CIRCULATOR POWER SUPPLY.
  • Page 7 L8148A,E,J AQUASTAT® RELAYS CAUTION INSERT CORNER OF SMALL SCREWDRIVER IN THIS Equipment Damage Hazard. NOTCH AND PRY STOP Improper procedure will damage equipment. UPWARD FROM DIAL FACE POINTER Never apply a jumper across (or short) terminals HIGH LIMIT B1, B2, or B3. This burns out the transformer. WHILE HOLDING STOP AWAY STOP FROM DIAL FACE WITH...
  • Page 8 95-6940EF—01 M.S. 04-20 | Printed in United States www.resideo.com © 2020 Resideo Technologies, Inc. All rights reserved. This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.
  • Page 9 Le modèle L8148E est offert avec une prise et un Réglage de la résistance anticipatrice de chaleur : 0,2 A transformateur 50 VA pour commander les vannes Resideo Smart Valve SV9500 et SV9600. Fiche signalétique – matières dangereuses : Pour obtenir plus de renseignements sur le composé...
  • Page 10 RELAIS AQUASTAT® L8148A, E, J REMARQUE : Ne pas serrer en utilisant le boîtier comme AVERTISSEMENT poignée. Risque d’explosion. 4. Remplir le système et s’assurer qu’il n’y a pas de Peut causer des blessures graves, entraîner la fuites. mort et des dommages matériels. 5.
  • Page 11 RELAIS AQUASTAT® L8148A, E, J l’excédent du capillaire juste en avant de la gaine S’assurer que l’extrémité élargie de l’adaptateur d’immersion pour éviter tout contact avec les épouse l’ouverture du boîtier. Placer l’étrier de la pièces électriques. gaine d’immersion pour qu’il épouse parfaitement la bride sur l’adaptateur de la gaine, puis serrer fer- REMARQUE : Certains modèles sont munis d’un tube mement la vis de l’étrier.
  • Page 12 RELAIS AQUASTAT® L8148A, E, J MISE EN GARDE THERMOSTAT 24 V Risque des dommages matériels. Peut entraîner un mauvais fonctionnement du système. L8148J 1. Si des régulateurs L8148E et J servent à alimenter les vannes de zone, la charge basse tension (24 V c.a.) ne doit pas dépasser 1,4 A.
  • Page 13 RELAIS AQUASTAT® L8148A, E, J T87F T87F T87F R845 R845 RELAIS R845 POMPE POMPE POMPE (SOUS TENSION) L8148A ORANGE BLANC C554 NOIR BRÛLEUR ET ALLUMEUR R8184G ALIMENTATION, FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES. LE BOÎTIER DE COMMANDE DOIT ÊTRE RACCORDÉ...
  • Page 14 RELAIS AQUASTAT® L8148A, E, J ZONE 2 ZONE 1 ZONE 3 THERMOSTAT THERMOSTAT THERMOSTAT 24 V 24 V 24 V V8043F V8043F INTERRUPTEUR AUXILIAIRE INTERRUPTEUR INTERRUPTEUR AUXILIAIRE V8043F AUXILIAIRE L8148J (SOUS TENSION) VANNE À GAZ mV POWERPILE® VANNE À GAZ BASSE TENSION (VR8300) THTR ALIMENTATION, FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE...
  • Page 15 RELAIS AQUASTAT® L8148A, E, J MISE EN GARDE INDICATEUR INSÉRER LE COIN D'UN PETIT TOURNEVIS DANS L'ENCOCHE ET ÉLOIGNER BUTÉE DU Risque de dommages matériels. LA BUTÉE DU CADRAN. RÉGULATEUR Une mauvaise façon de procéder causera des À MAXIMUM TOUT EN TENANT LA BUTÉE dommages au matériel.
  • Page 16 95-6940EF—01 M.S. 04-20 | Imprimé aux États-Unis www.resideo.com © 2020 Resideo Technologies, Inc. All rights reserved. This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.

Ce manuel est également adapté pour:

Aquastat l8148eAquastat l8148j