VISIBLE AND/OR AUDIBLE
SIGNALING APPLIANCES
ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGES 5 AND 6
I. INTRODUCTION
The Potter Electric models HS24-177, S24-177, EH-24, HS-24, S-24, HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG,
CHS-24R, CS-24WR, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP,
CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP are high quality audible and/or visible signaling appliances. The high intensity strobe utilizes
a Xenon flash tube that generates a high-intensity flash visible from all angles. This appliance is intended to provide a visible, audible or audible/visible, depending on the model, notification
signal for the purpose of life safety and property protection. The HS-24, S-24, CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R, CS-24WR are provided with a slider
switch which allows for candela selection at the installation site; the candela intensities which can be selected are 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd. The HS24-177 and S24-177 are fixed
candela units; the candela intensity which can be ordered is 177Cd. The HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP,
CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP,
CSLP-24WR-WP are fixed candela units, available in a 75 candela intensity only. This appliance is ideal for any occupancy that requires notification appliances per the applicable building or fire
code or wherever dependable alarms are required.
The HS24-177, S24-177, HS-24, S-24 strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired. The HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP,
CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R, CS-24WR, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP,
CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP strobe is listed in
compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General Signaling. Additionally, colored lens models CHS-24A, CS-24WA, CHS-24B, CS-24WB,
CHS-24G, CS-24WG, CHS-24R, CS-24WR comply with the polar dispersion requirements of ANSI/UL 1971.
II. LOCATION
This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA
documents that provide standards on notification appliances for protective signaling systems. The HS24-177, S24-177, EH-24, HS-24, S-24, CHS-24A, CS-24WA, CHS-24B, CS-24WB,
CHS-24G, CS-24WG, CHS-24R, CS-24WR are intended for indoor installations only; this appliance is not listed for outdoor or drip proof applications. The HS-24-WP, HSLP-24-WP, S-24-WP,
SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP,
CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP are intended for indoor or outdoor installations; this appliance is rated for outdoor or drip proof applications
when used in conjunction with the WPBB or WPLPBB Enclosure.
Wall mounted strobe and horn/strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in. (2.4m)**. Spacing shall be
in accordance with Table A. If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used. Wall mounted
horn only appliances shall have their tops above the finished floors at heights of not less than 90 in. (2.30m) and below the finished ceilings at heights of not less than 6 in. (152mm). Different
mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met.
III. MOUNTING, ROUGH-IN BOX AND RUN WIRING
This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes. Conduit entrance to boxes should be
selected to insure sufficient wiring clearance.
1. Run a minimum 18 gauge insulated 2 or more conductor cable.
2. Mount a box for each remote signaling appliance. Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block
receptacle. Place housing over mounted assembly and screw together with single screw at the bottom of the signal. Cover screw with plastic tab.
NOTICE: WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL. INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS
TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF
THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM
BEING PLACED UNDER THE SAME TERMINAL.
Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2013 Edition
Table A
Maximum Room Size
Meters
6.10 x 6.10
8.53 x 8.53
9.14 x 9.14
12.2 x 12.2
13.7 x 13.7
15.2 x 15.2
16.5 x 16.5
16.8 x 16.8
18.3 x 18.3
19.2 x 19.2
20.7 x 20.7
21.3 x 21.3
24.4 x 24.4
27.4 x 27.4
30.5 x 30.5
33.5 x 33.5
36.6 x 36.6
NA = Not allowable
39.6 x 39.6
HS24-177, S24-177, HS-24 AND S-24 PRODUCT INFORMATION
Minimum Required Light Output ( Effective Intensity, Cd)
One Light
Feet
per Room
20 x 20
15
28 x 28
30
30 x 30
34
40 x 40
60
45 x 45
75
50 x 50
94
54 x 54
110
55 x 55
115
60 x 60
135
63 x 63
150
68 x 68
177
70 x 70
184
80 x 80
240
90 x 90
304
100 x 100
375
110 x 110
455
120 x 120
540
130 x 130
635
HS24-177, S24-177, EH-24, HS-24 & S-24 SERIES
ANSI/UL & CAN/ULC COMPLIANT
HS-24-WP, HSLP-24-WP, S-24-WP & SLP-24-WP SERIES
CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G,
CS-24WG, CHS-24R & CS-24WR SERIES
CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP
CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP
CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP
CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP & CSLP-24WR-WP SERIES
ANSI/UL & CAN/ULC COMPLIANT
Four Lights per Room
(One Light per Wall)
NA
NA
NA
15
19
30
30
30
30
Distance from Ceiling to Top of Lens
37
greater than or equal to 24"
43
less than 24"
60
60
CAUTION:
95
Strobe light must be
95
installed within 16 feet
135
of the pillow when used
135
in a sleeping area.
185
**Effective Intensity Requirements for Sleeping Areas
Visible Notification Appliance
Intensity
110cd
177cd
550-0593
Page 1

Publicité

loading

Sommaire des Matières pour Potter HS24-177

  • Page 1 The HS-24, S-24, CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R, CS-24WR are provided with a slider switch which allows for candela selection at the installation site; the candela intensities which can be selected are 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd. The HS24-177 and S24-177 are fixed candela units;...
  • Page 2 THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE WILL NOT BE EFFECTIVE. 24VDC CLEAR Lens Indoor Strobe Current Ratings HS24-177 and S-24 and HS-24 Regulated 24VDC...
  • Page 3 CHSLP-24A-WP, CHS-24B-WP, CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP). Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Potter Electric AVSM synchronization protocol. Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute the horn, if available.
  • Page 4 5. Return to: Potter Electric Signaling Company, LLC 1609 Park 370, Hazelwood, MO 63042. Prior to returning, call the Potter Electric field service department at 1-800-325-3936 to obtain a RMA number.
  • Page 5 CAN/ULC S525 and/or CAN/ULC S526. This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the National Building Code of Canada, CAN/ULC S524 and local codes that provide standards on notification appliances for protective signaling systems. Potter Electric recommends spacing notification appliances in compliance with CAN/ULC S524.
  • Page 6 LIMITED WARRANTY For a period of 60 months from the date of manufacture (or as long as required by applicable law), Potter Electrical Signal Company, LLC warrants to you the original purchaser that your appliance will be free from defects in workmanship and materials under normal use and service.
  • Page 7 à glissière qui permet de sélectionner l’intensité lumineuse au moment de l’installation; voici les intensités pouvant être sélectionnées : 15 cd, 30 cd, 60 cd, 75 cd ou 110 cd (24 V c.c. seulement). Les modèles HS24-177 et S24-177 offrent une intensité lumineuse fixe qui peut être commandée, soit 177 cd. Les modèles HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP offrent une intensité...
  • Page 8 LE STROBOSCOPE DOIT ÊTRE VU PAR UNE PERSONNE QUI DORT. SI LA PERSONNE SE TOURNE LA TÊTE OU SI ELLE NE PEUT ÊTRE ALERTÉE PAR LE SIGNAL VISUEL, LE STROBOSCOPE NE SERA PAS EFFICACE. Caractéristiques nominales de courant du stroboscope intérieur à lentille TRANSPARENTE de 24 V c.c. Séries HS24-177 et Séries HS24-177 et Tension stabilisée Tension stabilisée...
  • Page 9 CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP). w Sélectionner le mode continu et laisser le FACP commander l’avertisseur ou choisir le mode temporel et synchroniser les avertisseurs au moyen du AVSM protocole de synchronisation Potter Electric. w Utiliser le AVSM protocole de synchronisation Potter Electric, s’il est disponible, pour assurer la synchronisation et couper l’avertisseur.
  • Page 10 5. Retourner à : Potter Electric Signaling Company, LLC 1609 Park 370 Hazelwood, MO 63042. Avant de retourner l’appareil, appeler Potter Electric au 1 800 325-3936 pour obtenir un numéro d’autorisation de retour (RMA) du Service à...
  • Page 11 Code du bâtiment canadien, de la norme CAN/ULC S524 et des codes locaux établissant les normes pour les appareils de signalisation des systèmes de signaux de protection. Potter Electric recommande de disposer les appareils de signalisation conformément aux exigences d’espacement de la norme CAN/ULC S524.
  • Page 12 être utilisés qu’à des fins informationnelles et ne doivent pas servir à remplace un avis juridique professionnel. Potter n’assumera aucune responsabilité quant aux mesures ou activités qui pourraient être, ou ne pas être, prises ou effectuées à la suite de ces renseignements.