Télécharger Imprimer la page

TDK-Lambda Vega 750 Manuel D'installation page 14

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 5
Vega 750 Instruction Manual
Environmental Specifications:
Description
Use
Temperature
Humidity
Altitude
Pressure
Orientation
Material Group
Pollution Degree
Overvoltage Category
Class
Weight
IP Rating
* 3000m for 60601-1 2
nd
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth - 2.25 - 2.35kVDC
Primary mains circuits to transformer core - 4.25 - 4.35kVDC**
Primary mains circuits to secondary -4.25 - 4.35kVDC**
Outputs to each other and to earth are isolated to 200VDC.
**This test is not possible with Y capacitors fitted to the unit as damage to these capacitors may occur. It is also
necessary to short circuit the outputs together and to earth
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
UL/CSA62368-1 UL Recognised. C-UL for Canada
IEC / EN62368-1 - CE and UKCA mark.
IEC/EN60950-1, IEC/EN62368-1, IEC/EN 61010-1 and IEC/EN60601-1 - CB Report and Certificate.
UL/CSA 61010-1 : UL + C–UL approval
UL/CSA 60601-1/ANSI/AAMI ES 60601-1 - UL + C -UL approval
CE marking when applied to any Vega 750 product indicates compliance with the Low Voltage Directive in that it
complies with EN62368-1 and with the RoHS Directive.
UKCA marking when applied to any Vega 750 product indicates compliance with the Electrical Equipment (Safety)
Regulations 2016 in that it complies with EN62368-1 and with the Restriction of the Use of Certain Hazardous
Substances in Electrical and Electronic Equipment Regulations 2012
Fusing: Internal fuses (F1): 16A/250V or 10A/250 fast acting HBC fuse 6.3x32 mm.
Symbols:
AC
EARTH
N
Operation
0 to 50°C (derating 2.5%°C above 50°C to 65°C -
Not covered by approvals).
5 to 95% RH non-condensing
-200m to 5000m*1 2
54kPa to 106kPa.
Horizontal with chassis lowest, on either side or
vertical with the airflow upwards.
ed, IEC inlet and cooling options D and E.
N – Neutral
L
Indoor
Ed)
nd
IIIb
2
II
I
2 kg (Dependent on configuration)
IPX0
L – Live
N
L
Page 14 of 26
Storage
-
-40°C to +85°C
5% to 95% RH non-
condensing
-200m to 5000m.
54kPa to 106kPa
All
17161 issue 20, November 2021

Publicité

loading