4. Power cables connection
4. Insert the Normal AC source cable through the cable gland.
5. Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the Input Bypass AC
jumper
and the UPS Input Bypass jumper inside the UPS I/O cover refer to the UPS User Manual)
4
6. Insert the Output cable through the cable gland.
7. Connect the wires to the Output terminal blocks.
8. Tighten the cable glands.
9. Slide back and secure the ModularEasy I/O cover
with the 2 screws.
3
10. Check EBM connected to UPS.
11. Connect the two UPS together with the 9PX parallel cable and lock it.
Use of specific parallel cable is mandatory for first start up and optimal use.