Press Enter to switch
M09
Other Paramaters
A
B
C
D
Press Enter to switch
M10
Defrost
E
F
Ref. #
P/N
Designed by
Checked by
Approved by - date
File name
IAN
ROGER
2023-03-17
HSS306080CTRL
1
1
2
Control Temp.select: Inlet Temp.
UNIT MODE
Ot00
Unit mode: Three Function.
BMS Settings
OTHER PARAMETERS
BMS Network:Disable
Delta Temp.Set: 15°C
Low Temp.Set: 4°C
OTHER PARAMETERS
Ot02
High Temp.Set: 64°C
Delta Temp.Deloading
Setp Diff:
4.0°C
Delta Temp.Keeping
OTHER PARAMETERS
Ot02
Setp. Diff:
5.0°C
Quit Deloading Setp
Diff:
4.0°C
Low Oulet Temp.Deload
Setp Diff:
1.0°C
Low Outlet Temp.Keep
OTHER PARAMETERS
Ot02
Setp. Diff:
2.0°C
Quit Deloading Setp
Diff:
3.0°C
High Oulet Temp.Deload
Setp Diff:
6.0°C
High Outlet Temp.Keep
OTHER PARAMETERS
Ot02
Setp. Diff:
7.0°C
Quit Deloading Setp
Diff:
8.0°C
Limited Deloading Interval
Time:
OTHER PARAMETERS
Ot02
Limited Time Limited
Deloading Rate:
1.0%
Deloading Delay:
Three vale
Start Dealy: 15s
OTHER PARAMETERS
Ot03
Stop Delay: 5s
Pump
Start Speed: 100%
OTHER PARAMETERS
Ot03
Start Delay: 5min
Start Internal: 3min
Pump
Max.Speed: 100%
OTHER PARAMETERS
Ot04
Min.Speed: 50%
EVI Management.
OTHER PARAMETERS
Ot05
Enabke Vapor Inj: Enable
OTHER PARAMETERS
Ot05
EEV2_Control_Mode:
Discharge Sperheart
Dig.Input cfg
Sel. NO/NC Contact
1 Flow Switch
NC
OTHER PARAMETERS
Ot06
2 Linkage Switch
NC
3 A/C Linkage Switch NC
5 Phase. Switch
NO
DEFROST
Df01
Defrost function: Enable
Min.speed to reverse
cycle changeover: 30.0rps
DEFROST PARAM.
Df02
EVD Forcing during defrost:
480stp
EVD Forcing when defrost
quit: 300stp
DEFROST PARAM.
Df02
EVD Forcing time: 40s
Compressor speed for
defrost: 65.0rps
DEFROST PARAM.
Df03
Pump speed for defrost:
100%
Def. Start setpoint: -1.0°C
DEFROST PARAM.
Df04
Def. End setpoint: 15.0°C
Ext. Def. Temp.: 15.0°C
Delta Temp.Between
DEFROST PARAM.
Df05
Ext.T and Con.Coil .T
5.0°C
Def. Min. Time:
1min
DEFROST PARAM.
Df06
Max. Duration:
8min
Def.Inter.Time:
45min
This drawing is the property of AQUA SOLANOR INC. It may not be used for any purpose other than the owner. AQUA
SOLANOR INC does not authorize the reproduction or conveyance of any information contained herein without prior written
Date
Scale
permission. This document is neither an engineering document, nor a construction document. Such documents shall be
produced in compliance with federal, provincial or municipal laws. The purpose of this document is to show the principle of
2022-09-23
NTS
operation of equipment.
2
3
3
4
Dig.Input cfg
Sel.NO/NC Contact
OTHER PARAMETERS
Ot06
4 Cool Switch NC
6 Heat Switch NC
Dig.Input cfg
Sel. NO/NC Contact
1 Fan High Speed: NC
OTHER PARAMETERS
Ot07
2 Fan Low Speed: NC
3 4 Way Valves:
NO
Dig.Input cfg
Sel. NO/NC Contact
4 Pump:
NC
OTHER PARAMETERS
Ot08
5 Three Vlave:
NC
6 Crank Heater:
NC
Dig.Input cfg
Sel. NO/NC Contact
7 Chassis Heater:
NC
OTHER PARAMETERS
Ot09
8 Terminal Pump:
NC
6 Heater:
NC
B1 Probe Offset: 0.0
B2 Probe Offset: 0.0
OTHER PARAMETERS
Ot10
B3 Probe Offset: 0.0
B4 Probe Offset: 0.0
B5 Probe Offset: 0.0
OTHER PARAMETERS
Ot11
B6 Probe Offset: 0.0
B7 Probe Offset: 0.0
B8 Probe Offset: 2.0
OTHER PARAMETERS
Ot12
B9 Probe Offset: 0.0
2s
B10Probe Offset: 0.0
OTHER PARAMETERS
Ot13
B12 Probe Offset: 0.0
3s
Press, Probe Filter
Filter thr. 0.02bar
OTHER PARAMETERS
Filter Time: 3000ms
EEV Evap.Press.Probe
S1 Alarm Delay:
60S
OTHER PARAMETERS
Ot14
Min.: 0.0bar
Max.: 34.5bar
Pump Direction Signal
OTHER PARAMETERS
Ot14
0%=10V, 100%=0V
EEV Evap.Press.Probe
Min.: 0.0bar
OTHER PARAMETERS
Ot15
Max.: 45.0bar
EVI Evap.Press.Probe
OTHER PARAMETERS
Ot16
Min.: 0.0bar
Max.: 34.5bar
EVI Management
OTHER PARAMETERS
Ot17
Vap Inj Rot Speed Set:
45.0rps
Condenser coil Temp. probe
error or offline Automatic
DEFROST PARAM.
Df07
dfrost every: 60min
4-way valve changeover timing
Start defrost: 10s
DEFROST PARAM.
Df08
Stop defrost: 10s
Dripping time: s
DEFROST PARAM.
Df09
Dripping time: 10s
Condenser fan froce on
DEFROST PARAM.
Df10
discharge Press.SetP 35.0bar
Diff.
2.0bar
Defrost switch press
compensation.
Yes
DEFROST PARAM.
Df11
Exhaust pressure
25.0bar
Suction presure
7.0bar
DEFROST PARAM.
Df12
Defrost manual: Disable
AmbTemp
<
=-10.0
DEFROST PARAM.
Df13
Start delta Temp.: 5.0°C
Interval time: 75min
-10.0
<
AmbTemp
<
=-2.0
DEFROST PARAM.
Df14
Start delta Temp.: 6.0°C
Interval time: 65min
4
5
6
EVI Management
Vap Inj Disch SH Set:
OTHER PARAMETERS
Ot18
28.0°C
Vap Inj Disch SH Diff:
5.0°C
EVI Management
Vap Inj T External ICH
OTHER PARAMETERS
Ot19
Set point: 70.0°C
Diff: 1.0°C
EVI Management
Vap Inj T External HP
OTHER PARAMETERS
Ot20
Set point: 13.0°C
Diff: 1.0°C
Fan Delay
OTHER PARAMETERS
Ot22
Delay Off:
5s
Antifreeze Prevent
Interval Time: 30min
OTHER PARAMETERS
Ot23
Antifreeze2 Compresser
Request:
50.0%
The Unit Srtandby For
60min Start Running
OTHER PARAMETERS
Ot23
The Pump 3mins
Comp. Alarm Unit Can
Not Run, Delay 60min
OTHER PARAMETERS
Ot23
OTHER PARAMETERS
Start Running The
Pump 3 Mins
Comp.Alarm Unit Can
Not Run,Delay 60min
OTHER PARAMETERS
Ot23
Start Running the Pump
3mins
OTHER PARAMETERS
Low Ambient Temp
Alarm Setpoint. -25.0°C
OTHER PARAMETERS
Ot23
Low Ambient Temp
Alarm Diff.
2.0°C
LENGUAGE
En.Function: Enable
Min.Req.Thrs.: 35.0%
COMPRESS OIL MNG
Ot24
Speed Thrs.: 40.0rps
CHANGE PASSWORD
Act.Delay: 60min
Speed Force: 60.0rps
COMPRESS OIL MNG
Ot25
Force Time: 3min
INITIALIZATION
Oilrecover And Defrost
COMPRESS OIL MNG
Ot25
Max Speed Set 70.0rps
Heat Fan Day Mode:
Low Fan Ambient Set:
INITIALIZATION
Ot25
25.0°C
High Fan Ambient Diff:
2.0°C
Cool: Fan Press Mode
INFORMATION
Discharge Press Set
Ot25
23.0bar
Open Press Diff 4.0bar
Close Press Diff 3.0bar
AmbTemp
<
=-2.0
Start delta Temp.: 7.0° C
DEFROST PARAM.
Df15
Interval time: 50 min
Set without defrosting for a
long time:
DEFROST PARAM.
Df15
Low temp.run exceeds 240min
Comp.run exceeds 10min
2305 46th AVENUE, LACHINE (QC) H8T3C9
5
6
7
8
Heat: Fan Press Mode
Discharge Press Set
Ot25
9.0bar
A
Open Press Diff 4.0bar
Close Press Diff 3.0bar
Fan Type Classification
Ot25
Fan Address 55
Ot25
Fan Drive Type Carel
Minimum Speed 200rpm
Ot25
Maxinum Speed 800rpm
Speed FAN
Able
Alarm Diff
200rpm
Alarm Delay
60s
FAN
Ot25
Offline Alarm
Delay
180s
Fan Commum Alarm Stop
NO
Ot25
Fan Min Speed
20.0%
B
Fan Max Speed 100.0%
Cool Minimum Set 12.0°C
Ot25
Heat Maximun Set 55.0°C
NET Settings
NO
Address:
1
Ot26
Unit Catagory:
Slave
Enable Hotwater Mode
(Slave):
NO
Remote/BMS Cards
Address 1 Baud19200
Ot26
BMS Card
Address 1 Baud 19200
Language: ENGLISH
ENTER to Change
ESC To Confirm
C
Show Mak Time
23
Insert New
PasswoManufact: 1234
Alarm Initialization
Delete Alarm Logs? NO
Clear AutoReset
Counters?
NO
Enable Buzzer?
NO
DEFAULT
INSTALLATION
Defaut Value:
NO
Code:
1 2 2
Ver.: HEATPUMPBLDC
Ot30
Date:
2022_02_09
OS:
4.8.002
D
E
F
ANNEX_"C"_04
Revision
Sheet
DWG.NO.:HSS306080CTRL
0
4
7