Télécharger Imprimer la page

S+S Regeltechnik RHEASREG WFS-1E Notice D'instruction page 6

Publicité

Les langues disponibles

Les langues disponibles

G
®
RHEASREG
WFS
Mechanical wind vane switch RHEASREG
monitoring of gaseous, non-aggressive media. The flow sensor is used as a flow controller or air flow monitor in air conditioning ducts, in air intake
or exhaust devices of ventilators or electric heating registers (also for contaminated, oily air).
TECHNICAL DATA
Switching capacity:
(Contact load)
Contact:
Housing:
Housing dimensions:
Base body:
Moving arm:
Vane:
Cable connection:
Housing temperature:
Operating difference:
Electrical connection:
Protection class:
Protection type:
Standards:
FUNCTION
Monitor:
Installation:
RHEASREG
®
WFS
Vane switch, mechanical, with paddle
Type ⁄ WG01
Switch-on value
min.
WFS
W F S -1E
2.5 m ⁄ s
Spare part
PWFS-08
Spare paddle for WFS (Stainless steel vane)
®
WFS with switching output, in an impact-resistant plastic housing, with stainless-steel paddle, for flow
15 (8) A; 24...250 V AC
at 24 V AC min. 150 mA
dustproof microswitch as
single-pole, potential-free changeover contact
plastic, UV-resistant,
material polyamide, 30 % glass-globe reinforced,
colour traffic white (similar to RAL 9016)
108 x 70 x 73.5 mm (Thor 2)
galvanised steel
brass
stainless steel V2A (1.4301)
cable gland, plastic (M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm)
–40...+85 °C
≥ 1 m ⁄ s
0.14 - 1.5 mm
2
, via screw terminals
I (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU, low-voltage directive 2014 ⁄ 35 ⁄ EU
Contact 1 - 3 breaks when flow rate drops to the preset value.
Simultaneously, contact 1 - 2 closes and
can be used as signal contact.
Device is factory-set to the minimum switch-off value,
which can be increased by turning the range adjusting screw clockwise.
vertical in horizontal air ducts.
Min. smoothing distance = 5 x duct diameter upstream and downstream of vane.
For airspeeds > 5 m ⁄ s, vane is to be trimmed at the marked spots.
Thereby the minimum switch-off value increases
to approx. 2.5 m ⁄ s and the minimum switch-on value
to approx. 4 m ⁄ s.
max.
9.2 m ⁄ s
Switch-off value
min.
max.
1 m ⁄ s
8 m ⁄ s
Rev. 2021 - V16
Item No.
1702- 3020- 0000-000
7700-0010- 2000- 000

Publicité

loading

Ce manuel est également adapté pour:

Rheasreg wfs