Figure 2: Breakaway tab
5 6
4
3
2
1
0
1.
Breakaway tab
Maintenance
When cleaning is necessary, the sensing chamber of the
detector easily unsnaps for field cleaning and service.
To clean the detector:
1.
Remove the detector from the base.
2.
Insert a screwdriver in the small slot where the detector
cap connects to the detector body. See Figure 3.
3.
Pry the detector cap off the detector body.
4.
Squeeze the optical block chamber where the two arrows
point, labeled "squeeze here."
5.
Pull off the optical block chamber.
6.
Blow off the optical block base in the detector body using
clean compressed air.
7.
Snap a new optical block chamber in place. Make sure
you line up the two arrows on the block chamber with the
snaps on the optical block base.
8.
Connect the detector cap to the detector body by rotating
the cap clockwise until it snaps into a locked position.
9.
Install the detector onto the base.
Note:
To verify the effectiveness of the cleaning,
recalibrate the device and run a device maintenance
report. Refer to the control panel technical reference
manual.
10. Test the detector and verify sensitivity.
Test
NFPA 72 and CAN/ULC S537 require a calibrated sensitivity
test upon installation and following any modifications or
additions to the system. The detector can perform this test and
generate a system sensitivity report.
To test the detector:
1.
Before initial testing, remove the dust cover from the
detector and notify the proper authorities that the fire
alarm system is undergoing maintenance and will be
temporarily out of service.
2 / 4
All manuals and user guides at all-guides.com
7
4 5
8
3
6
9
7
10
2
11
8
1
12
0 9
1
2.
Test the detector using Smoke-In-A-Can (model SM-200)
canned smoke. Carefully follow directions on the can to
avoid damage to the detector.
Figure 3: Detector disassembly
1.
Slot to insert screwdriver
2.
Optical block chamber
3.
Detector body
Specifications
Communication line voltage
Normal operating current
Alarm current
Smoke sensitivity range
UL
ULC
Environmental compensation
Compatible bases
Maximum distance from ceiling
wall-mounted
Storage temperature
Operating environment
Temperature
Humidity
Certification and compliance
Manufacturer [1]
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA
Year of
The first two digits of the date code (located on the
manufacture
product identification label) are the year of
manufacture.
North American
Meets: UL 268, ULC-S529-02
standards
Follow: NFPA 72, and CAN/ULC S524
[1] For warranty and return see "Contact information."
4.
Optical block base
5.
Detector cap
Maximum 20 Vp-p
45 µA
45 µA
0.67 to 3.66%/ft. obscuration
0.74 to 3.70%/ft. obscuration
Automatic
Standard: B4U, B4U-LP
Relay: RB4U
Isolator: IB4U
Audible: SB4U
12 in. (305 mm)
−4 to 140°F (−20 to 60°C)
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at
90°F (32°C)
P/N 3101066 • REV 04 • REB 23JAN13