LBSE-EM – LiteBox® Edge-Lit EM Battery Pack Accessory
Operation and Maintenance
Test Button Functions
1. While main power is on:
Press test button for <3 seconds to simulate "line power outage" or emergency mode". The light fixture
will come on using battery power.
Press test button for 3-6 seconds to initiate a brief self-check test routine (approx. 3-minute runtime).
The LED indicator will flash green @1 cycle/second as the system runs its check on the battery power
and circuit connections. Press the test button again at any time to stop the routine.
(Recommended monthly or per local code requirements)
Press test button for >6 seconds to initiate a full self-check test routine (90-minute runtime).
Note: The system will completely discharge the battery during this routine.
The LED indicator will quickly flash green @3 cycles/second as the system runs a more detailed ch eck
on battery power and circuit connections. Press the test button again at any time to stop the routine.
(Recommended yearly or per local code requirements)
2. While in Emergency Mode (line power outage):
Press test button for <6 seconds to turn off the unit. Press again to turn back on.
Press test button for >6 seconds completely shuts off the emergency output.
In this state, the system will not function unless the line power is reset.
LED Indicator Color/Functions
RED
Battery is charging
GREEN (steady) Battery is at full charge
GREEN (flashing)Self-check routine is in process
YELLOW Check system – possible battery replacement or system maintenance required
OFF
Indicates power outage; EM unit is in "Emergency Mode"
Minimum Charge Time: 24 Hours