Fuse Box:
J2 Connector
We recommend installing a
fuse box on each stage.
Cable Entry:
PC Communication
Punch holes at the bottom
port. Insert a
of the enclosure to allow
Comlink-1 or
Enabler card
wires to be introduced in the
(see next page).
controller. Do not drill the
top or side panels of the
enclosure.
Water Meter:
The water meter output
should be a dry contact and
should not pulse faster than
60 times a second (60 Hz).
A 22/12 AWG gauge cable
no longer than 2000 feet
(0.6 km) can be used to
connect the water meter.
Do not use a cable longer
than 2000 feet even if a
G
1
larger cable is used.
Do not run the meter
PMV-1
cable outside the building !
stage 1
Notes:
1. Installation of a good
quality alarm system is
strongly suggested to warn
of power failures and
high/low temperatures.
2. Provide a surge
protection (including
lightning protection) from
the power supply to the
controller and from the
control to the sensors.
Consult a certified
Static pressure
electrician if required.
sensor Dwyer
Gauge (optional)
3. Same phases must be
used to power the variable
fans and the controls on 3
phases power.
*Backup Thermostats:
ON/OFF Ouput Capacity:
The backup thermostats are
115VAC 1/4HP (187W), 230VAC 1/2HP
shown for illustration
(373W), 7.5 Amp Res. Max.
purposes only. Sufficient
backup thermostats must
We recommend installing external relays
be used to ensure
on "on/off" stages hooked to motors.
ventilation if the controller
loses power.
Connection
for top board
Potentiometer
(see overleaf)
Sensors (see overleaf)
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
I
J
K
L
G
1
PMV-1
stage 2
Relative humidity
Humidity sensor
(Old model)
from control
Coil
N.O.
COM
N.O.
COM
{
to distribution panel
stage input
VOLTAGE SELECTOR
115/230 VAC
Actuator (see overleaf)
WINCH
CLO OPN IN
STAGE 6
STAGE 5
STAGE 4 STAGE 3
RETURN
M
N
O
P
{
NO
C
Alarm
NC
-
0-10V
0-10V
0-10V +
output
#2
-
0-10V
0-10V
output
0-10V +
#1
Water meter
(optional)
1
2
3
4
THERMOSTAT
BACKUP*
(NOT INCLUDED)
sensor HS-1
(Optional)
Please scan the QR Code to access the complete
manual or visit the website.
Cumberland: http://www.cumberlandpoultry.com
AP: http://www.automatedproduction.com
Coil power source
{
Stage output
Mounting the Enclosure
on the Wall:
Leave a clearance of at
least 12" above controller
to allow the cover to be
removed for maintenance.
Variable Output Capacity:
115VAC 1/2HP (373W),
230VAC 1.5HP (1120W), 10 Amp Max.
Actuator (winch): Open/Close output,
V2 IN2 V1 IN1 L2/N
L
120VAC(0.17HP 124W), 240VAC
(0.5HP 373W), 30 VDC 5A Ind.
VARIABLE
FAN STAGE 1 MAX. OUTPUT 10 AMP.
VARIABLE
THERMOSTAT
BACKUP*
(NOT INCLUDED)
FAN STAGE 2 MAX. OUTPUT 10 AMP.
ON/OFF
FAN STAGE 3 MAX. OUTPUT 10 AMP.
ON/OFF
FAN/MIST STAGE 4 MAX. OUTPUT 10 AMP.
ON/OFF
FAN/HEATER/MIST STAGE 5 MAX. OUTPUT 10 AMP.
ON/OFF
FAN/HEATER/MIST STAGE 6 MAX. OUTPUT 10 AMP.
#891-00499
GSI Electronics Inc. • 5200 Armand Frappier Saint-Hubert, Qc • Canada J3Z 1G5 • Phone: 1-877-926-2777
E-mail: mtl_techsupport@agcocorp.com
12"
GND
CONTROLLER
L1
POWER SUPPLY
L2 (N)
230 VAC (115 VAC)
GND
STAGE 1
POWER SUPPLY
L2 (N)
230 VAC (115 VAC)
L1
GND
STAGE 2
L2 (N)
POWER SUPPLY
230 VAC (115 VAC)
L1
GND
STAGE 3
L2 (N)
POWER SUPPLY
230 VAC (115 VAC)
L1
GND
STAGE 4
L2 (N)
POWER SUPPLY
L1
230 VAC (115 VAC)
STAGE 5
GND
POWER SUPPLY
L2 (N)
230 VAC (115 VAC)
L1
GND
STAGE 6
POWER SUPPLY
L2 (N)
230 VAC (115 VAC)
L1
REV 07
WIRING DIAGRAM
EN
SMART CLIMATE 24
REV 02