Télécharger Imprimer la page

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

WARNING!
Always install equipment in accordance with
these instructions and in the manner consistent with
electrical codes and the authority having jurisdiction. Read
all instructions before mounting and wiring.
Overview
Alerton® VIP controller models:
VIP-363-HOA, a plant controller with expandable I/O
capability.
VIP-363-VAV, a VAV application controller with support
for one I/O expansion module.
Both models offer a high-performance, programmable
network programming system utilizing a built-in 4-port
Ethernet switch. It supports BACnet/Ethernet, BACnet/
IPv4, BACnet/IPv6 and RSTP protocols. The VIP-363-HOA
can also be configured for MSTP.
The VIP-363-HOA supports eight I/O expansion modules:
VXIO-322-HOA
VXIO-965-HOA
The VIP-363-VAV support one I/O expansion modules:
VXIO-322-HOA or
VXIO-965-HOA
Mounting
The VIP and VXIOs mount on a standard DIN rail:
vertically, with the connections on the right and left
sides of the device.
horizontally, with the connections on top and bottom.
The controller and both I/O expansion modules have a
locking clip. Mounting on a DIN rail ensures accurate
alignment of connectors between all modules. Or screw-
mount the VIP using the four mounting tabs, accessible
© Honeywell International Inc. All Rights Reserved
VIP Controller / VXIO Modules
under the covers. These mounting tabs may be broken off if
needed to save space when DIN rail mounting.
Note: Mount the controller prior to mounting any
necessary items (I/O modules).
WARNING! Always disconnect the controller and I/O
expansion modules from power before mounting.
To mount the devices on a DIN rail:
1
Holding the device with its top tilted in towards the
DIN rail, hook the two top flex snaps on the back of
the device onto the top of the DIN rail.
2
Push down and in to latch the two bottom latching
tabs of the device onto the DIN rail.
3
Properly ground the panel, then terminate
grounded components of power, communications,
and I/O wiring.
To remove the device from the DIN rail:
1
Push straight down from the top to release the
bottom tabs.
2
Rotate the bottom of the device out towards you
and pull the device up and away from the DIN rail
to release the bottom latching tabs.
Printed in MEXICO
31-00254EF-05
Installation Instructions
06-22
Page 1

Publicité

loading

Sommaire des Matières pour ALERTON VIP-363-HOA

  • Page 1 Read all instructions before mounting and wiring. Overview Alerton® VIP controller models: VIP-363-HOA, a plant controller with expandable I/O  under the covers. These mounting tabs may be broken off if capability. needed to save space when DIN rail mounting.
  • Page 2 Total power consumption must be based on the sum of the VA rating for each controller and I/O expansion module. The total must not exceed 100 VA. Figures 1 and 3 represent options for powering the I/O expansion modules separate from the VIP-363-HOA controller. VA Minimum...
  • Page 3 Tug gently on the cable to ensure that it’s securely terminated. Both I/O modules VXIO-322-HOA and VXIO-965-HOA can connect directly to the VIP-363-HOA or VIP-363- VAV. Note that the VIP-363-VAV only supports 1 VXIO expansion module. See below.
  • Page 4 NOT CONNECT SHIELDING TO ANY TERMINAL ON Connect the MS/TP+ to Terminal 1 and MS/TP- to THE DEVICE; connect shielding to a known earth ground Terminal 2 on the VIP-363-HOA. Use shielded 22 AWG, 2 at the panel/enclosure. conductor, twisted-pair cabling with characteristic impedance between 100 and 130 Ω...
  • Page 5 Canadian conformance statements This digital apparatus complies with CAN ICES-3 (B)/ NMB-3 (B). This device complies with Industry Canada license exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
  • Page 6 à l’arrière de l'appareil MSTP. sur le dessus du rail DIN. Appuyez et abaissez pour verrouiller les deux Le VIP-363-HOA prend en charge huit modules languettes de verrouillage inférieures de l'appareil d'extension d'E/S: sur le rail DIN.
  • Page 7 La consommation électrique totale doit être basée sur la somme de la valeur nominale VA de chaque contrôleur et module d’extension E/S. Le total ne doit pas dépasser 100 VA. Les figures 1 et 3 représentent les options qui permettent d’alimenter les modules d’extension d’E/S séparément du contrôleur VIP-363-HOA. Charge minimale en...
  • Page 8 HOA ou VIP-363-VAV. Notez que le VIP-363-VAV ne prend en charge qu'un seul module d'extension VXIO. Voir ci-dessous. Fig. 2 Contrôleur VIP-363-HOA, modules d'extension VXIO-232-HOA et VXIO-965-HOA Fig. 3 Module d’expansion monté à distance © Honeywell International Inc. Tous droits réservés Imprimé...
  • Page 9 EIA-485. Connectez le MS/TP+ à la borne 1 LE BLINDAGE À UN TERMINAL SUR L’APPAREIL; et le MS/TP- à la borne 2 du VIP-363-HOA.Utilisez un connecter plutôt le blindage à une prise de terre connue câble blindé à 2 conducteurs et à paires torsadées de du panneau ou de l’enceinte.
  • Page 10 Sensibilité électrostatique Le contrôleur VIP et ses composants peuvent être sensibles aux décharges électrostatiques (ESD). Utilisez des techniques appropriées de mise à la terre contre les décharges électrostatiques lors de la manipulation du produit. Dans la mesure du possible, manipulez toujours le produit par ses composants non électriques.

Ce manuel est également adapté pour:

Vip-363-vav