Barometric Damper
Regulador barométrico
Registre de tirage barométrique
Barometric Damper Installation Instructions
Sharp edges may cause serious injury from cuts. Use care when making duct openings and handling
ductwork.
• Turn off the HVAC system power before installing the barometric damper.
• Installation must be done in accordance with all applicable codes.
• Improper system installation could cause damage to the HVAC equipment. Check system operation
after installation.
1. IDENTIFY BYPASS DAMPER POSITION IN SYSTEM
a. The bypass damper must be located on the supply side of the HVAC equipment and upstream of any
supply ducts or zone dampers.
b. The bypass air can be supplied to the cold air return or into a conditioned space (dump zone).
2. INSTALL THE DAMPER INTO THE DUCTWORK
a. Install the bypass damper into the ductwork noting the airflow direction label.
b. The damper may be installed vertically, horizontally or at any angle.
c. Position the pressure regulator and adjustable knob such that they can be accessed after installation.
d. If the HVAC system is not in conditioned space, insulate the bypass duct per local codes.
e. ACCA Manual Zr recommends a manual hand damper be installed in the bypass duct to properly manage
airflow. Please visit aprilairepartners.com for more information.
Instrucciones para la instalación del regulador barométrico
ADVERTENCIA
Los bordes filosos pueden causar lesiones graves por cortes. Tenga cuidado al realizar aberturas en el
conducto y al manipular la red de conductos.
PRECAUCIÓN
• Desconecte la energía del sistema de calefacción, ventilación y aire acondicionado (Heating,
Ventilation, and Air Conditioning, HVAC) antes de instalar el regulador barométrico.
• La instalación debe realizarse conforme a todos los códigos correspondientes.
• La instalación incorrecta del sistema puede causar daños al equipo de HVAC. Controle el
funcionamiento del sistema después de instalarlo.
1. IDENTIFIQUE LA POSICIÓN DEL REGULADOR DE DERIVACIÓN EN EL SISTEMA
a. El regulador de derivación debe estar ubicado en el lateral de suministro del equipo de HVAC y corriente
arriba respecto de cualesquiera de los conductos de suministro o reguladores de zona.
b. El aire de derivación puede suministrarse hacia la zona de retorno de aire frío o en un espacio acondicionado
(zona de descarga).
2. INSTALE EL REGULADOR EN LA RED DE CONDUCTOS
a. Instale el regulador de derivación en la red de conductos teniendo en cuenta la dirección del flujo de aire
que figura en la etiqueta.
b. El regulador puede instalarse de manera vertical, horizontal o en cualquier ángulo.
c. Coloque el regulador de presión y la perilla ajustable de manera tal que se pueda acceder a ellos después
de la instalación.
d. Si el sistema de HVAC no se encuentra en un lugar acondicionado, aísle el conducto de derivación
conforme a los códigos locales.
e. El Manual Zr de los Contratistas de Aire Acondicionado de los Estados Unidos (Air Conditioning
Contractors of America, ACCA) recomienda instalar un regulador manual en el conducto de derivación
para administrar el flujo de aire de manera adecuada. Visite aprilairepartners.com para obtener más
información.
All manuals and user guides at all-guides.com
WARNING
CAUTION
3. ADJUST BYPASS DAMPER PRESSURE SETTING
a. Turn the system blower on at high speed (usually
cooling mode) with all zone dampers open.
b. Increase the pressure setting on the bypass
damper by turning the thumbscrew clockwise
on the regulator until the blade remains closed
without fluttering. See FIGURE 1.
c. Close all zone dampers except those going to the
smallest zone.
d. Make sure that the bypass damper is opening
under these conditions.
e. Check the airflow and noise levels in the smallest
zone to determine if they are acceptable.
– If the airflow is too high or noisy, lower the
pressure setting on the bypass damper.
– If the airflow is too low, increase the pressure
setting on the bypass damper.
FIGURE 1
CW (+)
TURN TO
ADJUST
CCW (–)
3. AJUSTE LA CONFIGURACIÓN DE LA PRESIÓN DEL REGULADOR DE DERIVACIÓN
a. Encienda el ventilador del sistema a alta velocidad
(por lo general, modo Refrigeración) con todos los
reguladores de zona abiertos.
b. Aumente la configuración de la presión del
regulador de derivación al girar el tornillo de
apriete manual en el regulador en sentido horario
hasta que la paleta quede cerrada y no se mueva.
Ver FIGURA 1.
c. Cierre todos los reguladores de zona, excepto los
de la zona más pequeña.
d. Asegúrese de que el regulador de derivación esté
abierto conforme a estas condiciones.
e. Verifique los niveles de ruido y flujo de aire en
la zona más pequeña para determinar si son
aceptables.
– Si el flujo de aire es muy alto o ruidoso,
disminuya la configuración de la presión en el
regulador de derivación.
– Si el flujo de aire es muy bajo, aumente la
configuración de la presión en el regulador de
derivación.
FIGURA 1
En sentido horario (+)
GIRE PARA
AJUSTAR
En sentido antihorario (–)
f. If the pressure setting was adjusted again, open
all zone dampers and verify that the bypass
damper remains closed.
g. To avoid too much air from being bypassed,
make a heating or cooling call (depending
on outdoor conditions) from the smallest
zone. After five minutes, measure the supply
air temperature and verify that it is within
normal operating limits. In cooling mode, the
temperature should be above 40°F. In heating
mode, the temperature should be below
150°F. Always refer to the HVAC equipment
manufacturer's specifications for these
temperature limits. If the supply air temperature
is not within normal limits, increase the pressure
setting on the bypass damper.
90-2227
f. Si ajustó la configuración de la presión otra
vez, abra todos los reguladores de zona y
verifique que el regulador de derivación
permanezca cerrado.
g. Para evitar que se derive demasiado aire,
encienda la refrigeración o la calefacción (según
las condiciones en el exterior) desde la zona
más pequeña. Después de cinco minutos,
mida la temperatura del aire de suministro y
verifique que se encuentre dentro de los límites
normales de funcionamiento. En el modo
Refrigeración, la temperatura debe ser superior
a 40 °F. En el modo Calefacción, la temperatura
debe ser inferior a 150 °F. Siempre consulte las
especificaciones del fabricante del equipo de
HVAC para obtener información sobre estos
límites de temperatura. Si la temperatura del
aire de suministro no se encuentra dentro de los
límites normales, aumente la configuración de la
presión en el regulador de derivación.
90-2227