Télécharger Imprimer la page

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

D16L-Fa LED Display Expander
Installation Sheet
EN FR
EN: Installation Sheet
LED operation
The LED display expander provides LED annunciation for up to
16 zones. The expander provides two LEDs for each zone.
Two LED display expanders can be installed in the panel.
LED operation zones 1 through 12 (and 17 through 28 if the
second LED expander is installed)
LED 1 - Alarm: Red LED flashes
LED 2 - Trouble: Yellow LED flashes
LED operation zones 13 through 16 (and 29 through 32 if the
second LED expander is installed)
LED 1 - Bicolor
Alarm: Red LED flashes
Non-alarm active: Yellow LED flashes
LED 2 - Trouble: Yellow LED flashes
Note:
LEDs go steady once the zone is acknowledged. LEDs
turn off once the zone is restored.
Figure 1: LED zone designations
LED 1
Zone 1
LED 2
LED
expander 1
LED 1
Zone 17
LED 2
LED
expander 2
© 2013 UTC Fire & Security. All rights reserved.
Zone 13
Alarm/Non-alarm
and trouble
zone LEDs
Zone 16
Zone 29
Alarm/Non-alarm
and trouble
zone LEDs
Zone 32
firealarmresources.com
LED installation
1.
Power down the panel and disconnect the batteries.
2.
Remove the screws securing the right and left side LED
display expander assemblies, and then remove each
expander assembly as shown in Figure 2.
3.
Remove the blank overlay from the front of the LED
display expander, and then install the new annunciator
overlay in its place as shown in Figure 2.
4.
Position the LED PCB on the expander assembly with the
holes in the PCB aligned to the pins in the expander
assembly as shown in Figure 3.
5.
Secure the PCB under the clips as shown in Figure 3.
6.
Connect the ribbon cable (P/N 7140196) from connector
J1 on the top expander to connector J6 on the main circuit
board as shown in Figure 3.
7.
Connect the ribbon cable from connector J1 on the bottom
expander to connector J2 on the left expander as shown in
Figure 3.
8.
Install the top and bottom LED display expanders and
secure using #6 plastite screws as shown in Figure 2.
9.
Identify each LED according to its programmed zone using
the labels provided.
10. Install the labels in the annunciator overlay.
11. Power up the panel and connect the batteries.
1 / 6
P/N 3101204 • REV 03 • REB 28JAN13

Publicité

loading

Sommaire des Matières pour Edwards D16L-Fa

  • Page 1 D16L-Fa LED Display Expander Installation Sheet EN FR LED installation EN: Installation Sheet Power down the panel and disconnect the batteries. Remove the screws securing the right and left side LED LED operation display expander assemblies, and then remove each expander assembly as shown in Figure 2.
  • Page 2 Figure 2: LED display expander assembly installation Top LED display expander assembly Annunciator overlay Blank Bottom LED overlay display expander #6 plastite assembly screw 2 / 6 P/N 3101204 • REV 03 • REB 28JAN13 firealarmresources.com...
  • Page 3 Figure 3: LED display expander installation Main circuit board Top LED display expander assembly Clip Alignment Bottom LED display expander assembly LED specifications Voltage 24 VDC Standby current 4 mA Active LED current One LED expander 48 mA Two LED expanders 96 mA Operating environment Temperature...
  • Page 4 Fixez la carte de circuits imprimés sous les attaches FR: Fiche D'Installation comme indiqué la Figure 3. Branchez le câble ruban (P/N 7140196) du connecteur J1 sur l’extenseur supérieur au connecteur J6 de la carte de Fonctionnement du voyant DEL circuits imprimés principale comme indiqué...
  • Page 5 Figure 3 : Installation de l’extenseur d’affichage DEL Carte de circuits imprimés Montage de l’extenseur du voyant DEL supérieur Voyant DEL de la cart de circuits imprimés Broche Axe d’alignement Montage de l’extenseur du voyant DEL inférieur Fiche technique du voyant DEL Voltage 24 VDC Courant en attente...
  • Page 6 6 / 6 P/N 3101204 • REV 03 • REB 28JAN13 firealarmresources.com...