Télécharger Imprimer la page
Edwards Genesis WG4 Consignes D'installation
Edwards Genesis WG4 Consignes D'installation

Edwards Genesis WG4 Consignes D'installation

Masquer les pouces Voir aussi pour Genesis WG4:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

Genesis WG4 Outdoor Horn Installation Sheet
EN FR
EN: Installation Sheet
Description
The Genesis WG4 Outdoor Horn is a life safety notification
appliance designed for indoor or outdoor use on ceilings or
walls. See Table 1 for a list of models and Table 2 for a list of
accessories.
For surface mount applications, mount the WG4 onto a
Model 449 electrical box using the gasket shipped with the
appliance. For flush mount applications where the mounting
surface is flush with the surface of the wall or ceiling, use the
WG4GSKT gasket kit.
Note that you need a Model 449 electrical box for waterproof
applications, or a standard mount 4 in. square box for all other
applications.
The horn includes field-configurable jumper options that allow
you to set the horn pattern to temporal or continuous, and the
horn volume to low or high.
Table 1: Models
Number
Description
WG4WF-H
Outdoor rated wall/ceiling horn, white with FIRE
marking
WG4WN-H
Outdoor rated wall/ceiling horn, white without marking
WG4RF-H
Outdoor rated wall/ceiling horn, red with FIRE marking
WG4RN-H
Outdoor rated wall/ceiling horn, red without marking
© 2012 UTC Fire & Security. All rights reserved.
Table 2: Accessories
Number
WG4WTS [1]
WG4RTS [1]
WG4GSKT [2]
[1] The trim skirt is outdoor-rated when used with the Model 449
electrical box.
[2] Not compatible with the trim skirts.
To synchronize horn operation, you must install a separate
synchronization source. See Table 3. When connecting the
horn to a listed control panel, verify synchronization operation
on the compatibility list for the corresponding panel.
Table 3: Compatible synchronization source models
Description
Auto-sync output
module
Genesis signal master -
remote mount
Booster or auxiliary
power supply
* Represents any number of additional characters
Installation
Install this device in accordance with applicable requirements
and in accordance with the local authorities having jurisdiction.
WARNING:
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
Notes
1 / 8
firealarmresources.com
Description
Outdoor-rated surface skirt, white, for Genesis WG4
horn or horn-strobe
Outdoor-rated surface skirt, red, for Genesis WG4
horn or horn-strobe
Appliance replacement gasket, flush mount
Number
SIGA-CC1S
GSA-CC1S
SIGA-CC2A
ADTG1M-RM
EG1M-RM
G1M-RM
APS10*
APS6*
BPS10*
BPS6*
EAPS10*
EAPS6*
Electrocution hazard. To avoid personal injury or
Electrical supervision requires that you break the wire run
at each terminal. Do not loop wires around the terminals.
Mount the Genesis WG4 Outdoor Horn horizontally or
vertically on either the wall or ceiling; place the electrical
box accordingly. See Figure 1.
P/N 3101999-ML • REV 1.0 • ISS 11APR12
SIGA-MCC1S
GSA-MCC1S
SIGA-MCC2A
MG1M-RM
XLSG1M-RM
ZG1M-RM
EBPS10*
EBPS6*
MIRBPS10*
MIRBPS6*
XLS-BPS10*
XLS-BPS

Publicité

loading

Sommaire des Matières pour Edwards Genesis WG4

  • Page 1 GSA-MCC1S SIGA-CC2A SIGA-MCC2A Description Genesis signal master - ADTG1M-RM MG1M-RM The Genesis WG4 Outdoor Horn is a life safety notification remote mount EG1M-RM XLSG1M-RM appliance designed for indoor or outdoor use on ceilings or G1M-RM ZG1M-RM walls. See Table 1 for a list of models and Table 2 for a list of...
  • Page 2 • When using a Model 449 electrical box, discard the gasket Figure 1: Horn mounting positions that is shipped with the box. • When using a trim skirt or a surface mount application, use the gasket that comes with the WG4 unit. —...
  • Page 3 Figure 3: Wire slot and jumper locations Maintenance Do not change the factory finish. Perform a visual inspection and an operational test twice a year, or as directed by the local authority having jurisdiction. This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
  • Page 4 0 (Ref) Description 80 and 110 −3 L’avertisseur sonore pour usage extérieur Genesis WG4 est un 39 and 125 −6 appareil de notification pour la sécurité des personnes, conçu [1] Angles are measured from a perpendicular axis; positive angles are pour une utilisation en intérieur ou en extérieur et pour un...
  • Page 5 « Caractéristiques techniques » de la page 7 pour obtenir Tableau 3 : Modèles de sources de synchronisation compatibles une liste des boîtiers compatibles. Description Numéro Passer le câblage existant à travers les fentes de guidage Module à sortie à sync. SIGA-CC1S SIGA-MCC1S automatique...
  • Page 6 Figure 2 : Vue éclatée de l’assemblage Figure 3 : Emplacements de la fente de guidage des câbles et des cavaliers (1) Vis du couvercle (6X) (4) Embase d’encastrement en (1) Fente de guidage des câbles (3) Cavalier du motif de (2) Couvercle avant option (2) Cavalier du volume de...
  • Page 7 Figure 4 : Schéma du câblage Temporel élevé 84,2 90,5 93,5 Temporel faible 81,7 85,4 88,1 dBA = décibels, pondérés A. UL 464 : niveau de sortie sonore mesuré dans une salle réverbérante à 3,05 m (10 pi.). Tableau 5 : Niveau de pression sonore (dBA), selon CAN/ULC- S525 Réglage du volume 16 V...
  • Page 8 Information réglementaire Fabricant Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Année de Les deux premiers caractères du numéro DATE fabrication MFG (situé sur l’étiquette d’identification du produit) correspondent à l’année de fabrication.