Wire stripping guide
1/4 in (~6 mm)
Strip 1/4 in (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
Caution: Exposing more wire may cause a ground fault.
Exposing less wire may result in a faulty connection.
Wiring diagram
From Signature controller
Notes
[1] Refer to the Signature loop controller installation sheet for
wiring specifications
[2] The SIGA-CR must be installed within the same room as
the device it is controlling
3.
Maximum 12 AWG (2.5 sq mm) wire; minimum 18 AWG
(0.75 sq mm) wire
P/N: 387023P REV: 7.0
2 / 4
Normally
Open
[2] [5]
TB2
Red LED
(Alarm / Active)
TB1
(+)
DATA IN
(–)
[1] [4]
or previous device
firealarmresources.com
Normally
Common
Closed
8
7
6
4
3
2
1
(+)
DATA OUT
(–)
To next device
[4] All wiring is power-limited and supervised
[5] Supervised and power limited when connected to power
limited source. If non-power limited, then all power limited
wiring in box must use FPL, FPLR, or FPLP cable or
equivalent per NEC. Power limited marking must
eliminated.
17JAN03
Compatible electrical box
Wall plate, white
(1-gang)
Green LED
(normal)
Installation Sheet
SIGA-CR - Control Relay Module