Installation arrangement
Recommended installation arrangement:
vertical, with pressure connections facing downward,
drain of possible condensed water (factory calibration).
Notice: Mount the transmitter with minimum 10 mm distance to
magnetic material. If this is not possible there is a failure of up to
minus 1 Pa for transmitters mounted on sheet steel.
ZP = Push Zero point reset.
The installation position is variable
by using the zero point reset button.
Pressure variations are resettable
after installation.
Ensure the power supply is not
interrupted when storing customer settings (ZP – reset,).

Connection diagrams

2 wire
Sauter AG - DDLU - Edition 09/2011 - 102677
ZP
3 wire
Universal
2 and 3 wire
19