Starting up
Turn the knob to Shutdown and press the
right-hand button for 5 seconds until H601
(maintenance menu reserved for the
installer).
Press OK.
The screen displays CF01.
5 sec.
CF01 – Correction of room temperature
measurement.
If there is a difference between the tempera-
ture noted (thermometer) and the tempera-
ture measured and displayed by the unit, the
menu acts on the measurement of the probe
so as to compensate for this difference (from
-4° C to +4° C in steps of 0.1° C).
Press + or – to make your choice, OK to
confirm it and go to the next menu.