A24V-3A-S
CONNECTION
Mains connection
•
Spring-loaded terminal block (marker J1)
•
Cross-section 0.5 to 1.5mm².
Connect and secure the power cable according to the attached diagram.
Caution: (Install a double-pole circuit breaker upstream of the power supply to comply with EN 60950).
Connection of the dry contact for mains presence information
•
Plug-in terminal block (marker J3)
•
Cross-section 0.14 to 1.5mm².
Connection of the 24VDC output
•
Plug-in terminal block (marker J4)
•
Cross-section 0.2 to 2.5mm².
USE
Connect J2 (Battery connection) and turn on the power.
Lighted signage :
•
LD 1: Mains present
•
LD 2: Battery charge
•
LD 3: Power output
•
LD 1, LD 2 and LD 3 on: Normal operation
•
LD 1 off: Mains not present (Check F1)
•
LD 2 off: Mains battery fault absent.
•
LD 3 off: Power supply overload (Check F2)
Dry contact mains presence
•
Present sector C and T are connected.
•
Absent sector C and R are connected.
Technical data sheet n° 600-0145C
www.castel.fr