C554A CADMIUM SULFIDE FLAME DETECTOR
While holding the mounting bracket in the slot, insert
the screwdriver in the other end of the slot (Fig. 4).
Bend the screwdriver, first to the left and then to the
right, to crimp the end of the mounting bracket and
hold it in position.
Remove the screwdriver and replace the cell.
Mount the new cell and bracket assembly in the
location of the old assembly.
BRACKET
SLOT
Fig. 3. Insert mounting bracket into socket slot.
SOCKET
BRACKET
LEADWIRE
60-0164EF—01
SOCKET
LEADWIRE
M7853
Fig. 4. Insert screwdriver to secure bracket in socket.
Oil Line Mounting
If desired, mount the C554A on the oil line using the oil line
adapter bracket and the mounting bracket supplied.
Remove the cell from the socket.
Insert the mounting bracket into the slot on the
socket (Fig. 3) as far as it will go.
NOTE: Bend the mounting bracket to fit, if
necessary.
While holding the mounting bracket in the slot, insert
the screwdriver in the other end of the slot (Fig. 4).
Bend the screwdriver, first to the left and then to the
right, to crimp the end of the mounting bracket and
hold it in position.
Remove the screwdriver and replace the cell.
Slide the mounting bracket into the sleeve on the oil
line adapter bracket. Push firmly to lock the cell and
the bracket assembly in position.
Mount the oil line adapter bracket on the oil line
using the screw and nut provided (Fig. 5).
SOCKET
INSERT SCREWDRIVER AND MOVE IN DIRECTION SHOWN BY
ARROWS TO SECURE BRACKET IN SOCKET
SLOT
SCREWDRIVER
2
SCREWDRIVER
BRACKET
M7855