Installation instructions
Please read carefully the installation
instructions. The used symbols mean:
Warning
This symbol point out a information,
ignoring of it can cause extensive
material damage. The security
information has to be observed.
Note
This symbol point out a information,
which indicate important details
concerning the use. Ignoring of it
can result in trouble.
General
JRG fine filters are only for filtering water. They in
no way replace any desired or necessary form of
water treatment (softening, sterilisation, etc.)!
I
14
Mounted position
For maintenance reasons, the fine filter must
be mounted vertically (with drain valve below).
A minimum space of 60 mm must be allowed
underneath so that the filter can be dismantled
for maintenance. If a hose is used for drainage,
this distance can be altered accordingly.
The JRG fine filter with transparent
filter cup should be installed so that it
is protected from intensive UV rays.
If the filter is installed in an aggressive vicinity
or in rooms with uncontrollable environment
(solvents and/or cleaning agent vapours, UV
radiation, etc.) the transparent filter cup must be
protected accordingly or replaced by a gunmetal
filter cup. We will be pleased to advise you in
cases of doubt.