Emergency light element for LED lamps NF15-A
General information:
The emergency light element must be used in a LED lamp in combination with a LED driver. In mains power operation, the current that is
supplied to the LED module is controlled by the LED driver. In emergency operation, the current for the LED module is supplied by a batte-
ry. The output current is controlled by the emergency light element.
Installation conditions:
The following conditions must be fulfilled in order for the emergency light element to be used in a LED lamp:
1. The current to be supplied to the LED module is direct current provided via two wires +/-.
2. You must use a LED array with an accessible 2 piece-wire bonding and without an integrated current limiting.
3. The LED module must be capable of withstanding a nominal output of 3 Watt. The maximum forward voltage must not exceed 100 Volt.
4. The voltage emitted by the driver must not be higher than 130 Volt. The maximum current flow in mains power operation must not be
higher than 2.5 A.
5. Do not use LED arrays with a grounded electric circuit. They are not suitable because of the system perturbation in emergency mode
which can not be filtered by the SG Device. As a consequence, the EMC limits would be neglected.
Compatibility:
Before inserting a NF15-A LED emergency light element into a LED lamp, compatibility with the LED module must be verified.
Safety:
For installation of the emergency light element, all conditions defined by the lamp must be considered additionally.
e.g. IP protection rate, etc.; all applicable standards and regulations must be adhered with.
Technical Data:
Permissible mains voltage:
Permissible mains frequency:
Power consumption:
Battery life:
Battery:
Permissible ambient temperature:
Charge time:
Protection class:
Protection rating:
Inspected according to:
Suitable for incorporation according to: EN 50172
Maximum output current:
Output power in emergency operation: 3 W
Self-test according to:
Supply voltage:
Open circuit voltage broken LED:
Wiring diagram:
Mains
Neutral N
Direct phase L
Switched phase L'
Self-test of visual display
Any possible faults (LED light, battery, etc.) are visualised by means of the 2-colour LED:
Green, permanently lit:
Not lit:
Red, flashing:
Red, intermittent flashing: Mains supply available, LED light source defective or not connected.
TULUX AG
Tuggen Tel +41 (0)55 465 60 00 / Fax +41 (0)55 465 60 01
Montageanleitung - Instruction de montage - Mounting instruction
230 V +/- 10%
50/60 Hz
3.5 - 4 VA with NiCd battery 4.8V; 1.8 Ah
1 h
NiCd 4.8 V; 1.8 Ah; +5°C....+50°C
Emergency light elem. +0°C....+50°C
24 h
I
IP 20
IEC 61347-2-13, EN 60598-2-22
2.5 A
EN 62034
20 - 130 V
150 V
Battery
CLX LED SG150-3.1
TULUX Nr.: NF15-A
L
N
Mains supply available, battery and LED light source connected correctly, battery is charged.
Mains supply available, mains voltage is below 160 V, deep discharge of the battery or device defective.
Mains supply available, battery not connected or defective.
Technische Änderungen vorbehalten
Modifications techniques sous réserve
Technical modifications excepted
Dimensions:
Control light
(must be clearly distinguishable)
+