to invert the water coil position:
To ease the water pipe connection of the coil, it is possible to invert the pipe coil outputs. To invert the coil position, remove all the panels,
unscrew the 8 fixing screws of the 2 output coil upright. Take out the coil and turn it over to have the pipe coil outputs at the other casing side.
Put back together all the panels inverting the mounting side.
Keep the water circulation way in the pipe coils as indicated on the label sticks on the casing.
output pipes are 1" gas diameter (26/34): male pipe thread.
Fastening of the accessories:
Damper and rectangular or circular couplings are fitted to the main casing with 4 HM8X20 screws.
The BECF casing is fitted to the main casing with 4 fasteners located on each side.
We recommend to use longitudinal feet, fitting them at the juncture of the two casings (see the drawing below).
Longitudinal feet
3. starting up
Before starting up the machine, make sure that the motor is connected to the main supply and all the panels secured.
4. Maintenance
Before manipulating the ventilator, make sure it is disconnected from the mains supply even if it has previously been switched off. Prevent the
possibility of anyone else connecting it while it is being manipulated.
Check regularly the filter clogging, measuring the differential pressure drop with the 2 tube connectors foreseen. The filter should be change
when its pressure drop reaches twice the initial pressure drop.
A safety differential pressure switch can be used to monitor the filter clogging.
a) g4 filter:
- Open the lateral panel turning the verrou with a large screwdriver
- Remove the G4 filter en le faisant glisser dans le caisson
- Replace a new filter and close the lateral panel
3