EVSS
VARIATEUR ELECTRONIC
AVEC TK
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
3
Modbus parity
4
Device type
5
HW version
6
FW version
7
Operating mode
8
Output override
9-10
11
Analogue input type
Ascending /
12
descending analogue
input mode
Maximum output
13
voltage
Minimum output
14
voltage
15
Enable off level
16
Off level value
17
Kick start / soft start
Kick start / soft start
18
duration
Remote control
19
functionality
Analogue input
20
functionality
21
Operation timer
22-30
31
Output override value unsigned int.
32-40
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-EVSS-FR-000 - 11 / 04 / 16
Data type
Description
unsigned int.
Modbus device address
unsigned int.
Modbus communication baud rate
unsigned int.
Parity check mode
unsigned int.
Device type (Read only)
unsigned int.
Hardware version of the device (Read only)
unsigned int.
Firmware version of the device (Read only)
Enables Modbus control and disables the DIP
unsigned int.
switch and trimmers
Enables the direct control over the output.
unsigned int.
Always settable. Active only if holding register 7
is set to 1.
Reserved, returns 0
Selects the analogue input type of the device.
unsigned int.
Always settable. Active only if holding register 7
is set to 1.
Ascending / descending analogue input mode.
Depends on the selected analogue input type.
unsigned int.
Always settable. Active only if holding register 7
is set to 1.
Maximum
settable
unsigned int.
settable. Active only if holding register 7 is set to 1.
Minimum settable output voltage. Always settable.
unsigned int.
Active only if holding register 7 is set to 1.
Enables off level. Always settable. Active only if
unsigned int.
holding register 7 is set to 1.
Off level value. Depends on the selected analogue
input type and ascending / descending analogue
unsigned int.
input mode. Always settable. Active only if holding
register 7 is set to 1.
Selects kick start or soft start. Always settable.
unsigned int.
Active only if holding register 7 is set to 1.
Sets the duration time. Always settable. Active
unsigned int.
only if holding register 7 is set to 1.
Sets the remote control input mode. Depends on
unsigned int.
the selected kick start or soft start mode. Always
settable. Active only if holding register 7 is set to 1.
Sets the analogue input functionality. Depends on
unsigned int.
the selected kick start or soft start. Always settable.
Active only if holding register 7 is set to 1.
Sets the operation time of the device when Timer
mode by remote control input or Logic mode by
the analogue input is selected. The operation
unsigned int.
time is additional to the kick start / soft start
duration times. Always settable. Active only if
holding registers 7 and 19 or / and 20 are set to 1.
Reserved, returns 0
Override value for the analogue output. Always
settable. Active only if holding register 8 is set to 1.
Reserved, returns 0
Retour à la Table des matières
Data
EVSS-DM = 3005
output
voltage.
Always
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
Default
Values
1—247
1
1 =
2 =
1—4
2
3 =
4 =
0 =
0—2
1
1 =
2 =
XXXX
0 x 0300 =
XXXX
0 x 0140 =
0 =
0—1
0
1 =
0 =
0—1
0
1 =
0 =
0—1
1
1 =
0 =
1 =
0—1
1
0 =
1 =
75 =
75—100
100
100 =
30 =
30—70
30
160 =
0 =
0—1
0
1 =
Ascending mode:
0 =
40 =
0 =
40 =
0—40
0
60—100
Descending mode:
100 =
60 =
100 =
60 =
0 =
0—1
1
1 =
0 =
0—60
10
60 =
0 =
0—1
0
1 =
0 =
0—1
0
1 =
0 =
0—200
60
200 =
0 =
0
0
30 =
30—100
100 =
9.600
19.200
38.400
57.600
8N1
8E1
8O1
HW version 3.00
FW version 1.40
Standalone
mode
Modbus mode
Disabled
Enabled
0—20 mA
0—10 VDC
10—0 VDC
0—10 VDC
or
20—0 mA
0—20 mA
75 % Us
100 % Us
30 % Us
00 % Us
Disabled
Enabled
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
Soft start
Kick start
0 s
60 s
Normal mode
Timer mode
Normal mode
Logic mode
0 s
200 s
0 % Us
30 % Us
100 % Us
13 - 17