Installer Menu - Sabiana T-MB2 Manuel D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLER MENU

With the INSTALLER menu it will be possible to view and modify the thermostat operating parame-
ters. Choice the parameter to modify by pressing the "+" or "-" buttons and confirm with the "M"
button. Once the parameter is selected, the display will show the value.
It will be possible to modify the value by pressing the "+" or "-" buttons.
Press the "M" button only one time to turn back to the parameter choice; to get out from the menu,
press the "M" button again.
FUNCTION
/PARAMETER
+/-3 MODE
Set the control into the +/- 3 configuration
T-MB NTC
Select the temperature probe fitted on the TMB or
on the unit (T1)
T DISP
Temperature view choice
°C/°F
Temperature unit of mesure change
OFS
Offset variation thermostat NTC probe
Irl
Hysteresis of relays
dEds
Dead zone central point
dEdr
Dead zone setup field
BMS
On/Off under supervision mode
dS
dS Set Variation Range with T–MB ± 9°C ± 3°C
T2-1
Status change from ventilation to cooling
T2-2
Status change from ventilation to heating
I-T2
T2 probe hysteresis
T3-1
Fan ON in heating
T3-2
Fan ON in cooling
I-T3
T3 probe hysteresis
F-t1
Anti-stratification waiting time
F-t2
Post ventilation duration
F-t3
Post ventilation time
t1ds
T1 air probe decompensation winter cycle (only for
Cassette)
Slu1
Min. speed tension
Scu2
Med. speed tension
SHu3
Max. speed tension
LLSI
Min. speed tension for fan auto winter
HLSI
Max. speed tension for fan auto winter
PFC
Proportional band in cooling
PFH
Proportional band in heating
LLSE
Min. speed tension for fan auto summer
HLSE
Max. speed tension for fan auto summer
Pt1
Pump intervention delay time
Pt2
OFF time in Summer
Pt3
ON time in Summer
tVIS
Temperature view type choice
( Vers. AU)
DESCRIZIONE
21
RANGE/SCELTA
ON = +/- 3 configuration activation
ON = TMB2 probe
OFF= Unit probe
TAMB = room temperature (related to the T-MB
NTC parameter)
T SET = view the SET temperature
°C / °F
± 3°C
0,5 ÷ 2,0°C
18 ÷ 30°C
1 ÷ 6°C
ON - OFF
± 9°C
15 ÷ 25°C
25 ÷ 35°C
> 30 ÷ 40°C
< 10 ÷ 25°C
2 ÷ 6°C
0,5 ÷ 2,0°C
1 ÷ 6
3 ÷ 8
6 ÷ 10
1 ÷ 6
5 ÷ 10
2,0 ÷ 6,0
2,0 ÷ 6,0
1 ÷ 6
5 ÷ 10
0 ÷ 300 sec.
30 ÷ 90 min.
0 ÷ 5 min.
0 = Wall control
1 = Probe fitted on the unit
2 = Current setpoint
English