PERFORMANCE
Number of cycles
Capacity
retention
120
100
90
80
70
60
0
0
Number of cycles is determined according to:
Unload velocity is made in C10 it means 10% of battery capacity per hour,
o
Then one complete charge is made.
o
Maximum number cycle is reached as soon as returned capacity represent 80%. After this
o
rate, the battery can still make cycle, but it cannot be considered in its cycling calculation.
Nb. DOD XX% means Depth Of Discharge XX% = unload at XX%
Capacity according to temperature
120%
100%
80%
60%
40%
20%
0%
-20°C
-15°C
A low temparture reduces remaining capacity.
For example, for a temperature of -5°C with an unload rate of 20% of the capacity (0,2C), the
available capacity will be 70%.
Also, in order to enjoy completely of Unibat batteries performances it is recommended having an
ambient temperature between 20 and 25°C.
26/46
DOD 100%
200
400
600
-10°C
-5°C
0°C
DOD 80%
800
1000
Number of cycles
+5°C
+10°C
+15°C
www.uniteck.fr
DOD 50%
DOD 20%
1500
2000
3000
+20°
+25°C
+30°C
4000
0,1C (A)
0,2C (A)
1 C (A)
2C (A)
+35°C
+40°C