UNIT DESCRIPTION
The CI-200 is a 24VDC Passive Infrared (PIR) occupancy sensor
which controls lighting or HVAC systems based on occupancy and/
or ambient light levels in a given area.
PIR sensing systems are passive systems which react to changes
in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them,
so careful consideration must be given to sensor placement.
COVERAGE PATTERNS
The CI-200 has a multi-cell, multi-tier Fresnel lens with a field of view
of 360°. The sensor has two lens pattern options. The Extended Range
Lens will cover up to 1200 sq ft when mounted from 8-12 ft. The High
Density/Reduced Range Lens will cover up to 500 sq ft when mounted
at 8-12ft.
Coverage shown in the diagrams below is maximum and represents
coverage for half-step walking motion, with no barriers or obstacles
Extended Range Lens
(Standard) CI-200
Side View
8 ft
2,4m
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
6,7 m
PLACEMENT
The effective coverage distances may be slightly less than the maximum sensing distance (see Coverage Patterns), depending upon
obstacles such as furniture or partitions, and this must be considered when planning the number of sensors and their positioning. See
the list below for approximate coverage distances for different types of motion.
Approximate coverage, for a mounting height of 8 feet:
Lens option
Walking motion
Extended Range
up to 22ft radius (1200 sq ft)
High Density
up to 12ft radius (500 sq ft)
The CI-200 sensor can be mounted at various heights. When you will be mounting at heights
other than 12 ft, be aware that as you decrease the mounting height, you will decrease the range
and increase the sensitivity to smaller motions. Conversely, when you increase the height, you will
increase the range and decrease the sensitivity to smaller motions. At heights of more than 12 -14
ft, you may start to significantly reduce sensitivity.
Often the best location to install a CI-200 in a closed office is off-center. Avoid placing a sensor
directly in line with an open door in which it has a clear view out, as the sensor may detect people
walking by.
All manuals and user guides at all-guides.com
360° Passive Infrared • Low Voltage Occupancy Sensor
Pasivo infrarrojo de 360° • Voltaje bajo Sensor de ocupación
Top View @ 8ft
44 ft
13,41 m
13 ft
7 ft
3 ft
0 3 ft
7 ft
13 ft
4m
2,1m
1m
1m
2,1m
4m
Workstation (hand motion)
12ft radius (500 sq ft)
9ft radius (300 sq ft)
IRP 360 ° • Détecteur de présence de basse tension
SPECIFICATIONS
Voltage Supply .........................20–30VDC (24VDC Typical)
Current Consumption ...............@24VDC, 24mA Maximum
Isolated Relay Rating ....................... 1A @24VDC or 24VAC
Operating Temperature.............. 32° to 131°F (0° to 55°C)
Time Delay Adjustment ................ 15 seconds–30 minutes
PIR Coverage
Model CI-200 ...................................... up to 1200ft2
Model CI-200-1 .................................... up to 500ft2
Light Level Adjustment ........................................ 1–190FC
Sensitivity Adjustment ...................... Minimum-Maximum
UL & CUL Listed
High Density/Reduced
Range Lens CI-200-1
Side View
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
6,7 m
CI-200
Top View @ 8ft
8 ft
2,4m
12 ft
9 ft
7 ft
5 ft
3 ft
0
3 ft
5 ft
3,7m
2,7m
2,1m
1,5m
1m
1m
1,5m
18'
Sensor
version 2
24 ft
7.32 m
7 ft
9 ft
12 ft
2,1m
2,7m
3,7m
12'

Publicité

Table des Matières
loading

Sommaire des Matières pour wattstopper CI-200

  • Page 1 Often the best location to install a CI-200 in a closed office is off-center. Avoid placing a sensor directly in line with an open door in which it has a clear view out, as the sensor may detect people walking by.
  • Page 2: Important

    All manuals and user guides at all-guides.com PLACEMENT CONTINUED For open office areas with partitions it is best to place sensors over intersections of four workstations Also avoid placing the sensors close to air ducts, as rapid air currents or the differences in temperatures may cause false activations.
  • Page 3: Sensor Adjustment

    To make the light level adjustment: (The final light level setting for normal operation should be made at a time when, with the lights off, the ambient light level is at the point where it is desired = ON = OFF for the lights to turn on.) = Factory Presets Visit our web site: www.wattstopper.com...
  • Page 4: Ordering Information

    3. Check that there is high voltage going into the power pack. 4. Try another power pack (if available). ORDERING INFORMATION Catalog# Description CI-200 20–30VDC Occupancy Sensor with Extended Range Lens (Standard) CI-200-1 20–30VDC Occupancy Sensor with High Density /Reduced Range Lens BZ-50...
  • Page 5: Spécifications

    27,95 m² (300 pi²) Le détecteur CI-200 peut être monté à différentes hauteurs. Lorsque vous le montez à des hauteurs autres que 2,4 m (8 pi), sachez que si vous baissez la hauteur de montage, vous diminuez la portée et augmentez la sensibilité...
  • Page 6: Instructions De Câblage

    All manuals and user guides at all-guides.com POSITIONNEMENT SUITE Pour les bureaux en espace ouvert avec des cloisons, il est préférable de placer les détecteurs au-dessus des intersections entre quatre postes de travail. Évitez également de placer les détecteurs près de conduits d’aération, car les courants d’air rapides ou les différences de température peuvent provoquer de fausses activations.
  • Page 7: Réglage Du Détecteur

    Réglez la temporisation et le niveau d’éclairage au minimum, puis restez immobile jusqu’à ce que les lumières s’éteignent (environ 15 secondes). Tournez lentement le bouton de niveau de luminosité en position maximum jusqu’à ce que les lumières s’allument, puis Consulter notre site web: www.wattstopper.com...
  • Page 8: Dépannage

    4. Essayez avec un autre bloc d’alimentation (si nécessaire). INFORMATIONS CONCERNANT LES COMMANDES N° de réf. Description CI-200 Détecteur de présence 20–30 V c.c. avec une lentille à portée étendue (standard) CI-200-1 Détecteur de présence 20–30 V c.c. avec une lentille à portée réduite/haute densité...
  • Page 9 27,95m² (300 pies²) El sensor CI-200 se puede montar a varias alturas. Cuando vaya a montar a otras alturas mayores a 12 pies, tenga en cuenta que a medida que disminuye la altura de montaje, disminuye el rango y aumenta la sensibilidad a movimientos más pequeños. Por el contrario, cuando se aumenta la altura, aumenta el alcance y disminuye la sensibilidad a los pequeños movimientos.
  • Page 10 All manuals and user guides at all-guides.com INSTALACIÓN PRECAUCIÓN DESCONECTE LA ENERGÍA DEL DISYUNTOR ANTES DE INSTALAR LOS PAQUETES DE ALIMENTACIÓN O LOS SENSORES. Una caja de conexiones 4-S se puede usar con un marco empotrable de 3”cuando los códigos de construcción locales obligan que las conexiones de bajo voltaje estén contenidas en una caja de conexiones.
  • Page 11: Ajuste Del Sensor

    • Si está presente, el problema puede ser con el sensor. Intente con otro sensor (si está disponible). • Si no hay voltaje, consulte la Lista de control del paquete de alimentación de alto voltaje, a continuación. Visite nuestro sitio web: www.wattstopper.com...
  • Page 12: Información Para Pedidos

    WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.

Table des Matières