Installation Instructions for Replacement Load Base Kit
SAFETY INSTRUCTIONS
Note: This instruction outlines recommended
installation procedure.
1. Turn OFF and lock out the power supplying the Safety
Switch.
2. Turn the Safety Switch OFF.
3. Remove Fuses.
4. Remove all load side conductors.
30 / 60 / 100 AMP LOAD BASE
©
2000 Siemens Energy & Automation, Inc.
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power
supplying thisSafety Switch be-
fore installing kit.
Replace the covers and shields
before restoring power to
switch.
MOUNTING
SCREW
Fig. 1
Replacement Load Base Kit
Item:
Catalog Number HBB21, HBB22, HBB62,
HBB63, HBB612M, HBB64 & HBB623
60-200 Amp General Duty &
For use with:
30-200 Amp Heavy Duty Fused VBII
Safety Switches
1
2
Page
of
500200A01
Pc. No.
5. Remove the two mounting screws and Load Base.
See Fig. 1.
6. Position replacement Load Base at appropriate fuse
position. See Figs. 1 and 2.
7. Install the two thread-rolling screws supplied with kit
and torque to 29 lb-ins.
8. Install Load side conductors.
9. Install Fuses.
10. Close cover before supplying power to switch.