Power Supply
The LP150/LP250 is a power-limited power supply and battery charger that will convert 120 VAC / 60Hz input into field-selectable 12 VDC
or 24 VDC Class 2 rated outputs (one continuous, one switchable). It is intended for use in applications with UL listing requirements (see
specifications below for specific listings).
This instruction covers:
LP150
PS cabinet + board (1.5A), battery wire kit, keylock
LP250
PS cabinet + board (2.5A), battery wire kit, keylock
LP250RDB4
PS cabinet + board (2.5A), battery wire kit, keylock,
RDB4 board *
Power Supply
with hinged cover
PS150/250 Specifications:
Input
LP150: 120 VAC, 1A, 60Hz
Output
LP150: 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 1.5A, Class 2 rated
LP250 (LP250RDB4): 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 2.5A, Class 2 rated
Output Protection
DC OUT and CONTROL OUT are protected from overload or shorts via self-resetting electronic protection circuit
Battery Protection
PTC
Environment
32°-120° F (0°- 49° C), up to 85% relative humidity, indoor use only, protected area
Compliance
UL294, UL603, Access control performance levels: Attack: I, Line security: I, Endurance: IV, Standby power: III
(LP150) and II (LP250/LP250RDB4), CSA22.2 NO. 205, CSFM, FCC
Battery Backup
Requires 12V, 7AH max. rechargeable sealed lead acid battery: (1) for 12V, (2) for 24V output.
Battery maximum dimensions: 3-3/4" H x 6" W x 3" D
See typical backup times in Section 2
See Section 8 for maintenance of battery
Control Input / Output
Input: Normally closed, requires dry contact rated at 24 VDC, 10mA
Output: Powered NC/NO contacts rated at 24 VDC, 2.5A
AC Status
Indicator: Green LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A
DC Output Status
Indicator: Red LED
Battery Status
Indicator: Red LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A
Enclosure
13" H x 12-5/8" W x 3-1/4" D (8 knockouts, 1/2" or 3/4")
LP150, LP250
LP150B, LP250B
LP250RDB4
Keylock
PS150/250
Enclosure
+ Board
Battery Wire Kit
LP150B
LP250B
LP250: 120 VAC, 1.2A, 60Hz
Installation Instructions
PS board only (1.5A), 4 mounting screws
PS board only (2.5A), 4 mounting screws
PS board
RDB4 board included
*
with LP250RDB4 only
and is covered in
separate instruction

Publicité

Table des Matières
loading

Sommaire des Matières pour Allegion Locknetics LP150

  • Page 1 *829767-00* LP150, LP250 LP150B, LP250B 829767-00 Power Supply Installation Instructions LP250RDB4 The LP150/LP250 is a power-limited power supply and battery charger that will convert 120 VAC / 60Hz input into field-selectable 12 VDC or 24 VDC Class 2 rated outputs (one continuous, one switchable). It is intended for use in applications with UL listing requirements (see specifications below for specific listings).
  • Page 2: Installation Overview

    Definitions: Normally closed contacts (NC) FACP - Fire Alarm Control Panel See Section 10 for an explanation of the Warnings and Cautions Normally open contacts (NO) ACC - Access Control Contacts used in this booklet. FSE - Fail secure (needs power to unlock) FS - Fail safe (needs power to lock) Installation Overview...
  • Page 3: Enclosure Dimensions

    Mounting CAUTION Product intended for indoor use only and within the temperature range specified. Mount unit in a protected area. Do not install in locations with exposure to rain or water. Mounting Hole Enclosure Dimensions Dimensions 12⁵⁄₈" 10¹⁵⁄₁₆" Mount in upright 11¹⁄₈"...
  • Page 4 Power Supply Board - Features and Operation L: Line, hot 120VAC, 60Hz G: Ground input voltage 120VAC N: Neutral WARNING Must be connected via rigid conduit. Neutral Earth Ground WARNING Non power-limited, Class 1 Keep power-limited wiring separate from non power-limited wiring. Minimum 1/4"...
  • Page 5 Typical Wiring FS & FSE device connected to PS board with FACP override FACP CONTROL MAGLOCK CONTROL LP150/250 E-STRIKE CONTINUOUS DC OUTPUT Operation: 1. CONTROL IN controls the operation of devices connected to the NO or NC terminals. 2. Opening of the FACP contacts will unpower the CONTROL OUT NC contacts and power the NO contacts.
  • Page 6 PS150B and PS250B Installation Enclosure cutaway shown for clarity Interior of enclosure 6-32 x 1/4" (4) Wire run lengths • Use the following table to estimate the gauge of wire required for the application. • Wire length based on 15% voltage drop at 12 or 24V using stranded copper wire. •...
  • Page 7 Secure enclosure door If No Keylock If Keylock Enclosure will be secured with 2 Remove knockout and insert key cylinder and secure with nut as shown screws as shown (done as last step) exterior of door #6 x 3/8" (2) interior of door AC Status indicator...
  • Page 8: Warnings And Cautions

    Maintenance Unit should be tested at least once a year for proper operation as follows: Voltage Output: • Verify the proper DC output voltage by measuring the DC+ and DC- terminals. Fire Alarm Release (if used): • Verify proper operation by opening the wiring to the CONTROL IN input. Confirm that the locks controlled by the CONTROL OUT output unlocked properly.
  • Page 9: Ces Instructions Couvrent

    LP150, LP250 LP150B, LP250B Bloc d’alimentation Instructions d’installation LP250RDB4 Le LP150/LP250 est un bloc d’alimentation limitée en puissance et un chargeur de batterie qui convertissent l’alimentation de 120 V/60 Hz en puissance nominale de classe 2 de 12 ou 24 VCC sélectionnables sur site (continue et commutable). Il est destiné à être utilisé dans des applications répondant aux exigences UL (voir les spécifications ci-dessous pour une liste spécifique).
  • Page 10: Aperçu De L'installation

    Définitions : Contacts normalement fermés (NC) FACP - Panneau de contrôle d'alarme Voir la section 10 pour incendie une explication des Contacts normalement ouverts (NO) avertissements et mises ACC - Contacts de contrôle d'accès FSE - Sécurité intégrée (besoin d'alimentation en garde utilisés dans pour déverrouiller) cette brochure.
  • Page 11: Dimensions Du Trou D'installation

    Installation MISE EN GARDE Le produit destiné à une utilisation en intérieur uniquement et dans la plage de température spécifiée. Installez l'unité dans une zone protégée. Ne l'installez pas dans des endroits exposés à la pluie ou à l'eau. Dimensions du Dimensions de trou d'installation l'armoire...
  • Page 12 Tableau d’alimentation - Caractéristiques et fonctionnement L: Ligne, alimentée 120 V, tension G: Mise à la terre d'entrée 60 Hz 120VAC N: Neutre Alimentée ATTENTION Doit être connecté via un conduit ridige. Neutre Mise à la terre ATTENTION Non limité en puissance, classe 1 Gardez le câblage limité...
  • Page 13: Câblage Typique

    Câblage typique Dispositif FS et FSE connecté à la carte PS avec neutralisation FACP FACP ENTRÉE DES CONTRÔLES MAGLOCK SORTIE DES LP150/250 GÂCHE CONTRÔLES ÉLECTRIQUE FSE SORTIE CC SORTIE CONTINUE Opération : 1. CONTROL IN contrôle le fonctionnement des appareils connectés aux bornes NO ou NC.
  • Page 14: Longueurs De Fil

    Installation de PS150B et PS250B Vue en coupe du boîtier pour plus de clarté Intérieur de l'enceinte 6-32 x 1/4 po (4) Longueurs de fil • Utilisez le tableau suivant pour estimer le calibre de fil requis pour l’application. • Longueur de fil basée sur une chute de tension de 15 % à...
  • Page 15: Porte Sécurisée

    Porte sécurisée Si pas de serrure Si une serrure est présente Le boîtier sera fixé avec 2 vis Retirez la découpe, insérez le barillet et fixez-le avec l'écrou comme indiqué comme indiqué (à la dernière étape) extérieur de la porte # 6 x 3/8 po (2) intérieur de la porte...
  • Page 16: Dépannage

    à la configuration de votre ressemblent à ceci : produit. Cela peut également vous diriger vers une autre partie de l'instruction. Customer Service 1-877-671-7011 www.allegion.com/us © Allegion 2019 Printed in Taiwan 829767-00 Rev. 06/19-b Canada 1-800-900-4734 www.allegion.ca...

Table des Matières