"HAL" for high temperature alarm ("LAL" fot the minimum allarm), followed
by the Maximum (minimum) temperature.
Then the "tiM" (tiMe) message is displayed, followed by the "Duration" in
h.mm.
3.
Then the instrument displays the temperature once again.
NOTE1: if an alarm is still occurring the "tim" shows the partial duration.
NOTE2: the alarm is recorded when the temperature come back to normal values
5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS
STILL OCCURRING
1.
Hold the SET key pressed for more than 3s, while the recorded alarm is
displayed. (the rSt message will be displayed)
2.
To confirm the operation, the "rSt" message starts blinking and the normal
temperature will be displayed.
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
1.
Push and immediately release the SET key: the display will
show the Set point value;
2.
Push and immediately release the SET key or wait for 5 seconds to display
the probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1.
Push the SET key for more than 2 seconds to change the Set point value;
2.
The value of the set point will be displayed and the
To change the Set value push the o or n arrows within 10s.
3.
4.
To memorise the new set point value push the SET key again or wait 10s.
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual
defrost will start.
6.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter's value operate as follows:
1. Enter the Programming mode by pressing the Set and
DOWN key for 3s (
2. Select the required parameter.
3. Press the "SET" key to display its value (now only the
LED is blinking).
4. Use "UP" or "DOWN" to change its value.
5. Press "SET" to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.5 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.5.1 HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the Set + n
key for 3s (LED 1 and
2. When a parameter is displayed keep pressed the Set+n
for more than 7s. The Pr2 label will be displayed
immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the "SET" key to display its value (Now only the
5. Use o or n to change its value.
6. Press "SET" to store the new value and move to the following parameter.
To exit: Press SET + o or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into "THE
FIRST LEVEL" (user level) by pressing "SET + n".
In HIDDEN MENU when a parameter is present in First Level the decimal point is
on.
6.6 HOW TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 s the o and n keys.
2.
The "POF" message will be displayed and the keyboard will be locked. At this
point it will be possible only to see the set point or the MAX o Min temperature
stored
3.
If a key is pressed more than 3s the "POF" message will be displayed.
6.7 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and n keys, till the "Pon"
message will be displayed.
MANUAL RNC 2007 053 PRELIMINARY T66 + XW60K.doc
Installing and Operating Instructions
LED starts blinking;
and
start blinking).
start blinking).
LED is blinking).
6.8 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by
holding the "o" key pressed for about 3 seconds.
The compressor operates in continuous mode for the time set through the "CCt"
parameter. The cycle can be terminated before the end of the set time using the
same activation key "o" for 3 seconds.
7. PARAMETERS
REGULATION
Hy
Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.
Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut
OUT is when the temperature reaches the set point.
LS
Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum
acceptable value for the set point.
US
Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum
acceptable value for set point.
Ot
Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to
adjust possible offset of the thermostat probe.
P2P
Evaporator probe presence: n= not present: the defrost stops by time;
y= present: the defrost stops by temperature.
OE
Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to
adjust possible offset of the evaporator probe.
OdS Outputs activation delay at start up: (0÷255min) This function is enabled
at the initial start up of the instrument and inhibits any output activation for
the period of time set in the parameter.
AC
Anti-short cycle delay: (0÷50 min) minimum interval between the
compressor stop and the following restart.
CCt
Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min)
Allows to set the length of the continuous cycle: compressor stays on
without interruption for the CCt time. Can be used, for instance, when the
room is filled with new products.
Con
Compressor ON time with faulty probe: (0÷255 min) time during which
the compressor is active in case of faulty thermostat probe. With COn=0
compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which
the compressor is OFF in case of faulty thermostat probe. With COF=0
compressor is always active.
CH Type of action: CL = cooling; Ht = heating.
DISPLAY
CF
Temperature measurement unit: °C=Celsius; °F=Fahrenheit. WARNING:
When the measurement unit is changed the SET point and the values of
the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and
modified if necessary).
rES
Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
Lod
Display : select which probe is displayed by the instrument: P1 =
Thermostat probe; P2 = Evaporator probe
dLy
display delay: (0-15 minutes) when the temperature increases, the display
is updated of 1 °C after this time.
DEFROST
tdF
Defrost type: EL = electrical heater; in = hot gas
dtE
Defrost termination temperature: (-50÷50 °C/ -58÷122°F) (Enabled only
when EdF=Pb) sets the temperature measured by the evaporator probe,
which causes the end of defrost.
IdF
Interval between defrost cycles: (0÷120h) Determines the time interval
between the beginning of two defrost cycles.
MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not
evaporator probe: timed defrost) it sets the defrost duration, when P2P = y
(defrost end based on temperature) it sets the maximum length for defrost.
dSd
Start defrost delay: ( 0÷99min) This is useful when different defrost start
times are necessary to avoid overloading the plant.
dFd
Temperature displayed during defrost: (rt = real temperature; it =
temperature at defrost start; SEt = set point; dEF = "dEF" label)
dAd
MAX display delay after defrost: (0÷255min). Sets the maximum time
between the end of defrost and the restarting of the real room temperature
display.
Fdt
Drip time: (0÷120 min) time interval between reaching defrost termination
temperature and the restoring of the control's normal operation. This time
allows the evaporator to eliminate water drops that might have formed due
to defrost.
dPo
First defrost after start-up: y = immediately; n = after the IdF time
dAF
Defrost delay after continuous cycle: (0÷23.5h) time interval between the
end of the fast freezing cycle and the following defrost related to it.
FANS
FnC
Fans operating mode: C-n= runs with the compressor, OFF during
defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the
compressor, ON during defrost; o-Y = continuous mode, ON during defrost;
Fnd
Fans delay after defrost: (0÷255min) Time interval between end of defrost
and evaporator fans start.
FSt
Fans stop temperature: (-50÷50°C/122°F) setting of temperature,
detected by evaporator probe, above which fans are always OFF.
ALARMS
ALc
Temperature alarms configuration: (Ab; rE)
temperature: alarm temperature is given by the ALL or ALU values. rE =
temperature alarms are referred to the set point. Temperature alarm is
enabled when the temperature exceeds the "SET+ALU" or "SET-ALL"
values.
ALu
MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this
temperature is reached the alarm is enabled, after the "ALd" delay time.
T66 – XW60K
PRELIMINARY
Ab=
absolute
2/4