Gas Supply Line; Burner Input Requirements - Jennair DIMENSION Guide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DIMENSION GUIDE

Gas Supply Line

■ Provide a gas supply line of 3/4" (1.9 cm) rigid pipe to the
range location. A smaller size pipe on longer runs may result
in insufficient gas supply. With propane gas, piping or tubing
size can be 1/2" (1.3 cm) minimum. Usually, propane gas
suppliers determine the size and materials used in the system.
NOTE: Pipe-joint compounds that resist the action of Propane
gas must be used. Do not use TEFLON
Flexible Metal Appliance Connector:
■ If local codes permit, a new CSA design-certified,
4 to 5 ft (122 to 152.4 cm) long, 1/2" (1.3 cm) or 3/4"
(1.9 cm) I.D., flexible metal appliance connector may be used
for connecting range to the gas supply line.
■ A 1/2" (1.3 cm) male pipe thread is needed for connection to
the female pipe threads of the inlet to the appliance pressure
regulator.
■ Do not kink or damage the flexible metal tubing when moving
the range.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe fittings
to obtain an in-line connection to the range. The rigid pipe must
be level with the range connection. All strains must be removed
from the supply and fuel lines so range will be level and in line.
■ Must include a shut-off valve:
Install a manual gas line shut-off valve in an easily accessible
location. Do not block access to shut-off valve. The valve is
for turning on or shutting off gas to the cooktop.
A.
Gas supply line
B.
Shut-off valve "open" position
C.
To range
†TEFLON
is a registered trademark of Chemours.
®
† tape.
®
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows for
proper operation:
Natural Gas:
Minimum pressure: 5" (12.7 cm) WCP
Maximum pressure: 14" (35.5 cm) WCP
Propane Gas:
Minimum pressure: 11" (27.9 cm) WCP
Maximum pressure: 14" (35.5 cm) WCP
Contact local gas supplier if you are not sure about the inlet
pressure.

Burner Input Requirements

Input ratings shown on the model/serial/rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a
rate of 4% for each 1,000 ft (304.8 m) above sea level (not
applicable for Canada).
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
1" (2.5 cm) water column pressure above the manifold pressure
shown on the model/serial rating plate.
Line pressure testing above 1/2 psi (3.5 kPa) gauge
[14" (35.5 cm) WCP]
The range and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi (3.5 kPa).
Line pressure testing at 1/2 psi (3.5 kPa) gauge [14" (35.5 cm)
WCP or lower]
The range must be isolated from the gas supply piping system
by closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psi (3.5 kPa).