OPTION 4 - Wiring MODBUS Control Signal
Fieldbus/Modbus Communication Cabling
The controller is able to communicate using Modbus RTU (RS485) to JetVent Fans, Vacon Variable Speed Drives (VSDs), and
fieldbus sensors.
Devices must be connected in a daisy chain with the controller at the start of the chain. No star connections are
§
allowed, and if a branch is required a Modbus repeater must be used.
IMPROPER WIRING CONFIGURATION
Maximum communication wiring length is 500m before a Modbus repeater is required.
§
Separate conduit should be used for power and communications cable. Keep communications cable away from
§
devices that generate EMC interference, such as powered antennas, transformers, contactors, and neon lights.
Low capacitance (<100 pF/m) twisted pair cable with shield and an impedance of approximately 120 ohms/m @
§
100 kHz.
BELDEN 3106A
o
END OF LINE X3
9
END OF LINE X8