STAR TECK CABLE FITTING
ST050-462 TO ST400-486
For jacketed cable, jacketed corrugated metal-clad cable with aluminum or steel armor
ASSEMBLY :
CAUTION: RISK OF ELECTRICAL SHOCK
Before installing or maintaining, verify
that all circuits are de-energized. Only to
be used with above listed cables.
INSTRUCTIONS :
RANGE OVER JACKET
STRIP LENGTH
TORQUE
CAT NO.
HUB SIZE
(IN)
(IN-LBS)
MIN.
ST050-462
0.525
ST050-464
0.600
1/2
300
ST050-465
0.725
ST050-466
1-1/4
0.825
ST075-467
0.880
3/4
600
ST075-468
1.025
ST100-469
1
700
1.187
ST125-470
1.350
ST125-550
1-1/4
1000
1.500
ST125-471
1.600
ST150-472
1.700
1-1/2
1200
1-3/4
ST150-473
1.900
ST200-551
1.900
ST200-474
2.100
2
ST200-475
2.300
ST200-476
2.500
ST250-477
2.380
2-1/2
ST250-478
2.580
ST300-479
2.790
1600
ST300-480
3
3.000
ST300-481
3.210
2-1/2
ST350-482
3.420
3-1/2
ST350-483
3.610
ST400-484
3.810
ST400-485
4
3.965
ST400-486
4.120
Note: Su x "S" after catalog number denotes a steel tting i.e. ST050-462S.
Note: Su x "SS" after catalog number denotes a stainless steel (type 316) tting i.e.ST050-462SS.
RANGE OVER ARMOR
(IN)
(IN)
A
THROAT DIA.
MAX.
MIN
MAX.
MIN. (IN)
0.650
0.415
0.570
0.395
0.760
0.490
0.680
0.485
0.885
0.615
0.805
0.612
0.985
0.715
0.905
0.612
1.065
0.770
0.985
0.819
1.205
0.915
1.125
0.819
1.375
1.077
1.295
1.039
1.625
1.240
1.545
1.182
1.625
1.390
1.545
1.370
1.875
1.490
1.795
1.370
1.965
1.590
1.885
1.557
2.187
1.790
2.107
1.600
2.187
1.790
2.107
1.715
2.375
1.990
2.280
1.995
2.565
2.190
2.485
2.057
2.750
2.390
2.656
2.057
2.640
2.240
2.560
2.230
2.840
2.440
2.750
2.430
3.060
2.640
2.970
2.630
3.270
2.870
3.190
2.860
3.480
3.042
3.390
3.032
3.690
3.270
3.590
3.260
3.870
3.440
3.770
3.430
4.030
3.600
3.930
3.590
4.185
3.755
4.065
3.745
3.340
3.910
4.220
3.900
Figure 1
Figure 3
Note: Design of tting does not require disassembly.
1. Select appropriate tting to accommodate the enclosure and cable used.
2. Determine the working length (the length of conductor required inside the enclosure or device).
Remove a portion of the outer jacket to expose the armor, cut armor using a hacksaw and trim the
outer jacket to adjust the exposed armor strip length, as indicated in the table (Figure 1 and 2).
CAUTION: Do not nick or cut the conductor insulation.
3. Feed cable through gland nut opening and push until cable armor hits end stop (Figure 3).
4. Tighten gland nut to the torque speci ed in the table (Figure 4).
Type H.L.A. CSA certified. Class I, II, III. CSA File No. 23086.
Suitable for Class I locations when used in combination with a certified Class I sealing fitting, as required by the
applicable electrical code.
UL Listed File No. E38947.
Fittings meet sealing requirements for locations
Type 4, 4x for aluminum and stainless steel,
Type 4 for steel.
MADE IN CANADA
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this
product for the user's intended application. Thomas & Betts warrants that this product will be free from defects in materials or workmanship for a period of
two (2) years following the date of purchase. Upon prompt notification of any warranted defect, Thomas & Betts will, at its option, repair or replace the
defective product. Misuse, misapplication or modification of Thomas & Betts Products immediately voids all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER
WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR
A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO
COST OF REPAIR OR REPLACEMENT OF THE PRODUCT AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY
INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
© 2014 Thomas & Betts. All rights reserved.
Page 1 of 2
Figure 2
Figure 4
Thomas
&
B
t e
s t
C
o
p r
r o
t a
o i
, n
M
e
m
p
h
, s i
T
e
n
n
e
s s
e
e
T
h
o
m
a
s
&
B
t e
s t
C
a
n
a
d
, a
t S
J -
e
a
n
s -
u
- r
R
c i
h
e
e i l
, u
Q
u
é
b
e
c
www.tnb.ca
T
A
0
0
9
0
4
F
P
a
g
e
2
f o
2

Publicité

loading

Sommaire des Matières pour Thomas & Betts STAR TECK ST050-462

  • Page 1 Figure 1 Figure 2 Instruction sheet for STAR TECK CABLE FITTING ST050-462 TO ST400-486 Figure 3 Figure 4 For jacketed cable, jacketed corrugated metal-clad cable with aluminum or steel armor ASSEMBLY : CAUTION: RISK OF ELECTRICAL SHOCK Before installing or maintaining, verify that all circuits are de-energized.
  • Page 2 Figure 1 Figure 2 Feuille d’instruction pour RACCORD À CÂBLES STAR TECK ST050-462 À ST400-486 Figure 3 Figure 4 Pour câbles Teck sous gaine ou câbles sous gaine métallique ondulée avec armure en aluminium ou en acier ASSEMBLAGE : ATTENTION: RISQUE DE CHOC ÉLECTRIQUE Avant l’installation ou la maintenance, véri er Note: Le raccord est conçu de manière à...

Ce manuel est également adapté pour:

Star teck st050-464Star teck st050-465Star teck st050-466Star teck st075-467Star teck st075-468Star teck st100-469 ... Afficher tout