TESTING THE THERMOSTAT
Heat Test
1. Slide Function switch to Heat
position. Heat mode screen is
displayed.
2. Adjust set temperature so it is 5 degrees above room
temperature.
3. Resistance heat should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees below
the room temperature and the heat should turn off.
Note: There is a 3 minute time delay and a 3 minute
minimum run time for the compressor when it turns
on/off. (On some models, the fan may also have a
minimum run time/off time delay).
14