Installation
"Network information"
When the network device is integrated to the LAN / Modbus net by Ethernet, configure the following parameters:
IP Address: Allow to modify the IP of the Network device port ("192.168.0.4" by default).
Mask: Ask to your IT technician for the proper value ("255.255.255.0" by default).
Gateway: LAN gateway address ("192.168.0.1" by default).
"Serial Information"
When the network device is integrated to the Modbus net by serial port RS485, configure the following parameters:
RS485: 9600 / 19200 Bps ("19200" Bps by default)
RS485: None / Odd / Even parity ("Even" by default)
Modbus Id: 1~128 ("1" by default)
Polarization: Communication polarization ("Disabled" by default)
N O T E
This part is not available for the HC-A64NET
"Units Id Configuration"
Automatic address can be done by pushing
Manual address configuration can be done by the assignation of each Id to a specific H-LINK addresss
-
Outdoor unit address (Ou) and Indoor unit address (Iu)
Confirm the configuration by pressing
Refresh button shall be pressed when modifiy the units conneced to the net
N O T E
This part is not available for the HC-A64NET
7
PMML0351A rev.1 - 10/2015