Owner's Manual
ULTRA-SAFE EXP Series
Electric Forced Air Heater for Hazardous Locations
This manual covers installation, maintenance and repair parts.
CSA Approved for the following classified areas:
Class I, Divisions 1 & 2, Groups C & D
Class II, Divisions 1 & 2, Groups F & G
Operating Temperature Code T3C - 320F (160C)
Alternate Markings: Class I, Zones 1 & 2, Group IIB, T3 or T(160)
or
Class I, Divisions 1 & 2, Groups C & D
Class II, Divisions 1 & 2, Groups E, F & G
Operating Temperature Code T3C - 320ºF (160ºC)
Alternate Markings: Class I, Zones 1 & 2, Group IIB T3 or T(160)
See Data Plate for Specific Area Classification
For details on the particular hazardous environments having the potential for explosion, refer to Articles 500 through 516 of the
National Electric Code, and/or Section 18 of the Canadian Electric Code, Part I.
Page 1 of 16
ENM-2119-01 / HX-23-2199-83-3

Publicité

loading

Sommaire des Matières pour Heatrex ULTRA-SAFE EXP Serie

  • Page 1 Owner’s Manual ULTRA-SAFE EXP Series Electric Forced Air Heater for Hazardous Locations This manual covers installation, maintenance and repair parts. CSA Approved for the following classified areas: Class I, Divisions 1 & 2, Groups C & D Class II, Divisions 1 & 2, Groups F & G Operating Temperature Code T3C - 320F (160C) Alternate Markings: Class I, Zones 1 &...
  • Page 2 WARNINGS Installation and maintenance personnel should familiarize themselves with this manual and all the WARNINGS before installing or working on this heater to avoid potential hazardous conditions, severe property damage, personal injury or death. To reduce the risk of ignition of hazardous 11.
  • Page 3 See figure below for minimum installation clearances: GENERAL The air heaters are designed for comfort heating and should not be used in ambient temperatures exceeding 104ºF (40ºC). The units may be wall, pole or ceiling mounted. They utilize a hermetically sealed, liquid-to-air heat exchanger containing immersion type electric heating elements.
  • Page 4 Ensure conductors are of appropriate gauge size. The c.) Any room thermostat used with this heater must be of minimum gauge is stamped on the nameplate. Size all an explosion-proof type rated for the area input conductors according to accepted standards classification, open on temperature rise, rated consistent with the temperature rating of the wire being minimum 120VAC, 75VA inductive capacity.
  • Page 5 b.) Set the temperature control thermostat to a B. Mechanical: setting below the current room temperature. Never attempt to fill, drain or check the liquid level of c.) Energize the heater electrical supply circuit. the heat exchanger or check the action of the pressure d.) The heater fan should come on but the heater relief valve.
  • Page 6 To reinstall, slide the core through the bottom Check out and report any unusual or of the cabinet while an assistant lines up and questionable operating characteristics, such as installs the 3 heat exchanger mounting bolts. noise, vibration, loss of fluid, etc. Guide the heater lead wires back into the If heater operation appears normal, place the wiring enclosure.
  • Page 7 REPLACEMENT PARTS All replacements must be factory supplied to ensure safe heater operation. Mark wires and refer to wiring diagram to ensure proper electrical connections. Reference heater catalog number and item number in figures below when contacting factory for replacement parts. Contact factory for items not shown.
  • Page 8 Select the Figure that corresponds to your heater. FIGURE 1: FIGURE 2: ITEM DESCRIPTION ITEM DESCRIPTION Wiring Enclosure and Cover Wiring Enclosure and Cover Option Mounting Bridge Main Contactor Option Contactor Ground Lug Main Contactor Ground Lug Transformer Auxiliary Contact Transformer Main Mounting Bridge Auxiliary Contact...
  • Page 9 Manuel du Propriétaire Série ULTRA-SAFE EXP Chauffage électrique à Air Pulsé pour les Endroits Hasardeux Ce manuel explique l’installation, la maintenance et les pièces de rechange et de la réparation. CSA licencié pour les locaux suivantes classifiés: Classe I, Divisions 1 & 2, Groupes C & D Classe II, Divisions 1 &...
  • Page 10 Les Avertissements Le personnel d’Installation et de maintenance devraient se familiariser avec ce manuel et tous les AVERTISSEMENTS avant d’installer ou de modifier cet appareil de chauffage afin d’éviter des conditions hasardeuses potentielles, des dommages sévères des locaux, des blessures personnels ou la mort. 10.
  • Page 11 GENERAL Les appareils de chauffage d’air sont dessinés comme chauffage de confort et ne doivent pas être utilisés dans des températures ambiantes en excès de 104 degrés f. (40 degrés C.) Ces appareils peuvent être montés au mur sur un poteau ou au plafond. Ils utilisent un échangeur de chaleur liquide-à-l’air hermétiquement clos et contiennent des éléments de chauffage électriques type immersion.
  • Page 12 acceptées conformant à la classification de température du fil Regardez le schéma électrique et suivez les instructions ci- choisi. Au minimum choisissez un fil d’une certification pour 75 dessous: degrés C. a.) Ne cherchez pas à installer un interrupteur ventilateur L’installation correcte de l’appareil de chauffage exige qu’un fil exclusif dans un appareil de chauffage normal ni à...
  • Page 13 g.) Ajustez le thermostat plus haut que la température écrous de la structure supportante. De la même façon, ambiante. contrôlez les boulons et écrous de montage du moteur. h.) L’appareil de chauffage et le ventilateur devraient se De temps en temps, rassurez-vous que le moteur, le mettre en marche tous les deux ensembles.
  • Page 14 b. Détachez les conduits d’alimentation des Détachez les deux écrous utilisés pour attacher le thermorupteur haute-limite. contacteurs dans la boîte de câblage. c. Démontez l’union de conduit au centre de Levez et détachez la plaque de montage en tôle. Soigneusement soulever et enlever le thermorupteur haute- câblage sur le moteur.
  • Page 15 Eléments de Remplacement Tous remplacements doivent être fournis par la manufacture afin d’assurer l’opération sauve de l’appareil de chauffage. Notez et marquez les fils en vous adressant au schématique électrique afin d’assurer des connections correctes. En contactant la manufacture pour des éléments de remplacement, donnez le numéro du catalogue de l’appareil de chauffage et aussi le numéro des éléments dans les illustrations ci-dessous.
  • Page 16 Sélectionnez le schéma de votre appareil FIGURE 1: FIGURE 2: ITEM DESCRIPTION ITEM DESCRIPTION Boîte de câblage Boîte de câblage et couvercle Applique optionnel Contacteur principal Contacteur optionnel Mis-à-terre Contacteur principal Mis-à-terre Transformateur Contacteur auxiliaire Transformateur Applique principal Contacteur auxiliaire Applique principal FIGURE 3: FIGURE 4:...