Télécharger Imprimer la page

Danfoss EKE 347 Mode D'emploi page 16

Régulateur de niveau de liquide
Masquer les pouces Voir aussi pour EKE 347:

Publicité

User Guide | Régulateur de niveau de liquide, EKE 347
Modbus parameters
Software version: 1.62.xx
Label
Parameter name
r12
Main switch
R01
Liquid level setpoint
N07
Operation Mode
a02
Lower level limit
a01
Upper level limit
a07
Level alarm mode
a04
Lower delay
a03
Upper delay
a06
Lower level hysteresis
a05
Upper level hysteresis
a08
Function common alarm
a12
Oscillation detect band
a13
Oscillation detect timeout
a25
Force pump OFF in stopped mode
a14
IO Lower level limit
a15
IO Upper level limit
a16
IO Lower level hysteresis
a17
IO Upper level hysteresis
a18
IO Lower delay
a19
IO Upper delay
a20
IO Level limit
a21
IO Level delay
a22
IO Level hysteresis
a23
IO Level action
N03
Control Method
n35
Regulating principle
n04
P-band
n05
Integration time Tn
n34
Neutral zone
N06
Difference
n13
Period time for AKV/AKVA
n33
Minimum OD
n32
Maximum OD
o11
Language
o17
Output indication
K04
Login timeout
K06
Backlight timeout
o05
Password daily
K02
Password service
K03
Password commission
K05
Contrast
K01
Brightness
I09
System configuration
o31
Level signal setup
o32
Voltage at low liquid level
o33
Voltage at high liquid level
I06
Current at low liquid level
I07
Current at high liquid level
o34
Valve position setup
I02
Voltage at closed valve position
I03
Voltage at open valve position
I04
Current at closed valve position
I05
Current at open valve position
I18
Common alarm setup
I08
Multiple valve setup
I13
Multiple valve pattern
I10
Valve A capacity
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
Min
Max
Default
Unit
value
value
0
1
0
0
100
50
%
0
2
0
0
100
15
%
0
100
85
%
0
1
0
0
999
10
s
0
999
50
s
0
20
3
%
0
20
5
%
0
3
0
0
100
100
%
2
30
20
min
0
1
0
0
100
5
%
0
100
95
%
0
20
3
%
0
20
3
%
0
999
10
s
0
999
50
s
0
100
50
%
0
999
10
s
0
20
3
0
1
0
0
2
2
0
1
0
5
200
30
%
60
600
400
s
0
25
2
%
0,5
25
2
%
3
15
6
s
0
0
%
1
100
100
%
0
0
0
0
1
0
1
120
10
min
0
120
2
min
0
999
100
0
999
200
0
999
300
0
100
40
%
0
100
80
%
0
4
0
0
3
0
0
0
V
10
10
V
0
4
mA
20
20
mA
0
2
0
0
0
V
10
10
V
0
4
mA
20
20
mA
0
3
1
0
4
0
0
1
0
0
100
50
%
Deci-
Modbus
Locked
EEPROM
mals
PNU
by main
switch
0
3001
NO
YES
1
3002
NO
YES
0
3003
YES
YES
0
3004
NO
YES
0
3005
NO
YES
0
3006
NO
YES
0
3007
NO
YES
0
3008
NO
YES
1
3009
NO
YES
1
3010
NO
YES
0
3011
NO
YES
0
3012
NO
YES
0
3013
NO
YES
0
3117
NO
YES
0
3101
NO
YES
0
3102
NO
YES
1
3103
NO
YES
1
3104
NO
YES
0
3105
NO
YES
0
3106
NO
YES
0
3107
NO
YES
0
3108
NO
YES
1
3109
NO
YES
0
3110
NO
YES
0
3014
NO
YES
0
3015
NO
YES
1
3016
NO
YES
0
3017
NO
YES
1
3018
NO
YES
1
3019
NO
YES
1
3020
NO
YES
0
3021
NO
YES
0
3022
NO
YES
0
3023
YES
YES
0
3024
NO
YES
0
3025
NO
YES
0
3026
NO
YES
0
3027
NO
YES
0
3028
NO
YES
0
3029
NO
YES
0
3030
NO
YES
0
3031
NO
YES
0
3032
YES
YES
0
3033
YES
YES
1
3034
NO
YES
1
3035
NO
YES
1
3036
NO
YES
1
3037
NO
YES
0
3038
YES
YES
1
3039
NO
YES
1
3040
NO
YES
1
3041
NO
YES
1
3042
NO
YES
0
3043
YES
YES
0
3044
YES
YES
0
3045
NO
YES
0
3046
YES
YES
Enumeration
0 = Off | 1 = On
0 = Master | 1 = Slave | 2 = IO
0 = Time | 1 = Hysteresis
0 = Not follow | 1 = Follow up | 2 = Fol-
low low | 3 = Follow all
0 = Off | 1 = On
0 = Falling | 1 = Rising
0 = On/off | 1 = P-ctrl | 2 = PI-ctrl
0 = Low | 1 = High
0 = $ActiveLanguageList
0 = Level | 1 = OD
0 = ICAD+NC | 1 = ICAD | 2 = AKV/A+NC
| 3 = AKV/A | 4 = NC only
0 = AKS4100 | 1 = AKS41 | 2 = Current |
3 = Voltage
0 = Not used | 1 = Current | 2 = Voltage
0 = DO4 | 1 = High Alarm | 2 = DO3 | 3
= Disp only
0 = Not used | 1 = 2 same cap | 2 = 2 dif
cap | 3 = 3 same cap | 4 = 3 dif cap
0 = Parallel | 1 = Sequence
DKRCI.PD.RP0.A4.04 | 16

Publicité

loading