Télécharger Imprimer la page

S&P AIRSENS COV Mode D'emploi page 9

Publicité

Fig. 3:
Modbus
Output Coils (Read)
Register Output Coil
1
Invertir SetPoint
Reboot Factory
2
settings
3
General Reset
Discrete inputs (Read)
Register Discrete input
10001
Relay status
SW1
10002
10003
SW2
10004
SW3
10005
SW4
10006
SW5
10007
SW6
10008
SW7
10009
SW8
Alarm
10010
Data type Range
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
Data type Range
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
Default Comments
Output analogue signal 0-10V
0
/ 2-10V change and have an
inverse response
Modbus registers pass to
0
factory settings
0
General reset activated
Default Comments
OFF: Contact (NO) normally
opened
-
ON: Contact (NO) normally
closed
SW1.1
OFF: Set Point + Relay (MF1)
-
ON: Analogue output/Modbus
(MF2/MF3/MF4)
SW1.2
OFF: Analogue output 0-10V
-
(MF2)
ON: Analogue output 2-10V
(MF3)
SW1.3
-
OFF: Modbus (only reading)
ON: Control via Modbus (MF4)
-
No function
-
No function
-
No function
-
No function
-
No function
Error: Defective sensor,
communication fault or other
-
problem
OFF: Working correctly
ON: Alarm