PowPak
Installation
|
20 A Receptacle Control Relay Module
Part of the Vive Family
RMJS-20R-DV-B
120 / 277 V~ 50 / 60 Hz 20 A
With Softswitch
1.0 HP at 120 V~ 2.0 HP at 277 V~
RMJS-20RCCO1DV-B
1 SPST Output
With Softswitch and
UL 2043 Plenum Rated
Occupancy-Status CCO
Note for Replacement:
These products can replace RMJ-H20R-DV-B for
receptacle control.
Important Notes:
Please read before installing.
•
For installation by a qualified electrician in accordance with all local and
national electrical codes.
•
Note: Use copper conductors only.
•
Check to see that the device type and rating is suitable for the application.
•
DO NOT install if product has any visible damage.
•
If moisture or condensation is evident, allow the product to dry completely
before installation.
•
Operate between 32 °F (0 °C) and 131 °F (55 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
•
The 20 A Receptacle Control Relay Module turns ON automatically in response
to both a Radio Powr Savr wireless occupancy and vacancy sensor.
NOTE: Not intended for control of permanently installed lighting fixtures.
WARNING
Shock Hazard - May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
Entrapment Hazard - To avoid the risk of entrapment, serious injury,
WARNING
or death, these controls must not be used to control equipment
which is not visible from every control location or which could create
hazardous situations such as entrapment if operated accidentally.
Fire Hazard - To avoid the risk of fire, serious injury, or death,
WARNING
these controls must not be used to control equipment which is not
visible from every control location or which could create hazardous
situations such as fire if operated accidentally.
Important Note
Examples of such equipment which must not be operated by these controls include (but
are not limited to) motorized gates, industrial doors, space heaters, etc. It is the installer's
responsibility to ensure that the equipment being controlled is visible from every control
location and that only suitable equipment is connected to these controls. Failure to do so
could result in serious injury or death.
PowPak 20 A
Receptacle Control
Relay Module
Install in center of room to
maximize RF coverage.
Radio Powr Savr
Occupancy
Sensor
30 ft (9 m)
Maximum
Pico
Remote
Control
40 ft (12 m)
All Wireless Transmitters must be
installed within 30 ft (9 m) of the
PowPak 20 A Receptacle Control
Relay Module.
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
For FCC/IC information:
Please visit: www.lutron.com/fcc-ic
Lutron, Pico, PowPak and Softswitch are trademarks of Lutron Electronics Co., Inc.,
registered in the U.S. and other countries.
Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc.
Safari is a trademark of Apple Inc., registered in the U.S. and other countries.
Chrome is a trademark of Google Inc.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts
©2012-2017 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Required Components
For each system ensure you have:
At least one PowPak
20 A Receptacle Control Relay Module.
041611
(Occupancy-Status CCO Option Shown)
Rev. A
06/2017
Status
LED
Relay Toggle
+
Advanced
Operations
Contact
Relay Module
Closure
without
Output
occupancy-status
(CCO)
CCO also
(Class 2)
available.
PowPak Relay Module
Start Here
Install PowPak 20 A Receptacle Control Relay Module
1
Suggested Installation Location: Center of
room to ensure proper RF coverage of area.
When installing a PowPak 20 A Receptacle Control
Relay Module, use the supplied conduit nut and wire
the module as shown. For a Vive hub commissioned
system, identifying this unit will flash the LEDs, not
the receptacle load. If it will be difficult to view the
LEDs on the unit after installation, recording the serial
number is an alternate method of quick identification
as the identification in the setup tool will show the serial
number.
Serial number
23453463
00BB373A
If installing the unit inside a junction box, please see
Application Note #423
(www.lutron.com/TechnicalDocumentLibrary/048423.pdf).
For more information: www.lutron.com/powpakrelay
2
Programming with a Vive Hub
A
Use a smart device to configure the
B
Vive hub.
Vive
PowPak
|
Programming without a Vive Hub
Start Here
1
Associate Wireless Transmitters to PowPak 20 A Receptacle Control Relay Module
Before beginning this step, make sure that there are no other PowPak modules being set up within the same building. It is possible that Wireless Transmitters from
other systems can be incorrectly associated to this system.
A
Hold the Relay Toggle
button on the PowPak
20 A Receptacle Control
Relay Module for 6 seconds
to enter association mode.
Note: The status LED will
flash 4 seconds ON, 1
second OFF.
At least one Wireless Transmitter.
Pico Remote
Radio Powr Savr
Occupancy / Vacancy Sensor
Control
(10 maximum)
(10 maximum)
Wiring for a Duplex Receptacle:
Junction Box
Line/Hot (Black)
120 V~
50/60 Hz
Neutral (White)
Switched
Line/Hot (Red)
COM
(Common)
NO
NC
(Normally Open)
(Normally
Closed)
CCO operation affected only by
associated occupancy or vacancy sensors.
To 3rd-party
Room
equipment
Occupied:
NO = Close NC = Open
Note: CCO terminals accept 20 AWG to 16 AWG
Room
2
(0.5 mm
Unoccupied:
NO = Open NC = Close
Note: Do not tie the CCO to ground
u
Any receptacles that are controlled by an automatic control device must be marked with "u "
Labeling
located on the controlled receptacle outlet where visible after installation as stated in 2014 NECR
Article 406.3(E). Receptacle labels are included.
Open the Wi-Fi setting on the smart device and
C
Open a Safari
select the network that is similar to Vive-1a2b3c.
device. Type vive.lutron.com in the address bar.
Vive
B
Hold the indicated
button on a Wireless
Relay
Transmitter for 6
Toggle
seconds to associate
the device.* Repeat for
any additional Wireless
Advanced
Operations
Transmitters.
* If no g button, hold
"Lights Off" button.
Customer Assistance
CCO Information
• Some PowPak Relay Modules include a dry contact closure
output that provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and VAV
controllers.
• CCO provides both normally open (NO) and normally closed (NC)
maintained-type outputs.
Switching
Resistive
• CCO rated to switch resistive loads at
Voltage
Load
R
voltages up to 24 V only. To properly
0-24 V-
1.0 A
control inductive load types such as
0-24 V~
0.5 A
relays, solenoids, or motors,
refer to Application Note #434
Customer Assistance | 1.844.LUTRON1 U.S.A., Canada, and the Caribbean | +44.(0)20.7680.4481 Europe | +1.610.282.3800 Others | www.lutron.com/support
Wiring for Split-Wired Duplex Receptacle:
Line/Hot (Black)
120 V~
50/60 Hz
Neutral (White)
u
COM
Controlled 20 A
(Common)
Receptacle
NO
NC
(Normally Open)
(Normally
Closed)
Uncontrolled
CCO operation affected only by
20 A
associated occupancy or vacancy sensors.
Receptacle
Room
Occupied:
NO = Close NC = Open
Room
2
to 1.5 mm
) solid or stranded wire.
Unoccupied:
NO = Open NC = Close
NOTE: Do not tie the CCO to ground
or Chrome
browser on the smart
D
Follow the instructions on the screen to set up
®
TM
your system.
vive.lutron.com
vive.lutron.com
C
Hold the Relay Toggle button on
the PowPak Relay Module for 6
seconds to save association(s).
D
Permanently install wireless
transmitters
(consult individual component
installation guides for information).
www.lutron.com/support
Reset Factory Defaults
Note: In some instances it may be necessary to reset the
PowPak 20 A Receptacle Control Relay Module back to
factory default settings.
A Triple-tap the Advanced Operations ("ADV") button on the
Relay Module and hold until the LED begins to flash rapidly.
B Within 3 seconds of flashing, release and triple-tap the button
again and the LED will flash slowly indicating that the unit has
been reset to factory defaults.
Note: Any associations or programming previously set up with
the unit will be lost and will need to be re-programmed.
Junction Box
Note: This example is showing
a split-wired receptacle. The top
portion of the receptacle is not
Neutral (White)
controlled by the
Switched
u
20 A Receptacle Control Relay
Line/Hot (Red)
Module, while the bottom
portion is switched by the
20 A Split-Wired
20 A Receptacle Control Relay
Receptacle
Module.
To 3rd-party
equipment
Note: CCO terminals accept 20 AWG to 16 AWG
(0.5 mm
2
to 1.5 mm
2
) solid or stranded wire.
Note: For further information on set
up, programming, and troubleshooting
with a Vive system, please refer to the
installation instructions included with the
Vive hub or visit www.lutron.com/vive
Note: For programming the PowPak
Relay Module without a Vive hub see
Programming without a Vive Hub
below.
Troubleshooting
www.lutron.com
Load does
• Ensure breaker to the PowPak 20 A Receptacle
not respond
Control Relay Module is on.
to Wireless
• Ensure the load has been properly wired to the
Transmitter(s)
PowPak 20 A Receptacle Control Relay Module.
• Ensure Wireless Transmitter is properly
associated to PowPak 20 A Receptacle Control
Relay Module.
• Ensure Wireless Transmitter's battery is installed
correctly.
Wireless
• The maximum number of Wireless Transmitters
Transmitter(s)
have been associated to the PowPak 20 A
cannot be
Receptacle Control Relay Module. To remove
associated to
a previously set up Wireless Transmitter, tap
PowPak 20 A
the button used for association on the Wireless
Receptacle
Transmitter three times, on the third tap hold for
Control Relay
three seconds and then tap three more times.
Module