Installation instructions V1.8
MICO 2.10 Art.-No.: 9000-41042-0401000
Technical data:
Input values:
Input voltage:
+24V DC (SELV/ PELV)
Residual ripple of power supply
< 5% for one-phase, 2% for three-phase
Range of working voltage
18-30 VDC
Frequency of power ON/OFF max 1 Hz
Suppressor diode
36V
No reverse polarity protection
(0...+20%)
Total operating current:
20A
Maximum summation current of
+24V terminals:
40A
Output values:
Nominal output voltage:
24V DC, corresponding to the input voltage
Voltage drop at 10A per each load branch:
typical 0,2V
Turn ON capacity:
max. 20mF*
Internal fuse: 10A delay fuse for each channel
* Dependent on: component tolerance, conduit length, used power supply, load current, selected current range
Schematic circuit diagram:
Notice:
Please pay attention to wire heating in relationship of its cross section, ambient temperature, current and the
used fuse. The in 4 levels settable channel current serves as the wire protection and device protection
conform to EN60204-1, referring to the maximal permissible channel curren
installation instructions does not contain detailed information to all types of this product and may not consider
each fictitious case of erection, operation or installation.
Continuing information may be taken from the data sheet or from our homepage in the internet
http://www.murrelektronik.com.
Technical alterations are reserved at any time.
© 2005 Murrelektronik GmbH, Oppenweiler
All rights reserved. Each reprint, even in parts, requires our written consent.
Murrelektronik GmbH
P.O. Box 1165
Falkenstrasse 3
Murrelektronik Intelligent Current Operator
Signalling: See "Displays"
Environment:
Storing temperature:
-40° C to +80° C
Environmental temperature: 0 to +55° C
Cooling by natural convection
Safety:
Rated insulation voltage: 50V
Degree of pollution: 2
Classification of over-voltage III
Additional output protection:
10A fuse for each channel internal
(UL 248-14, UL File E10480).
Regulations:
EN 60529: Protective system - IP20
EN 61000-6-2: Immunity to interference
EN 61000-6-3: Interference emission class B
EN 60068-2-6: Oscillating test
EN 60068-2-27: Shock test
Weight: ca. 90g
Measurements LxWxD: 90x36x80 mm
24V DC
Melde 1-2
GND
+24
Taster
Control Logics
Reset
OUT
1
2
13
14
Load
Load
1
2
t.
For lucid reasons this
D-71567 Oppenweiler
Telefon +49(0)7191/47-0
D-71570 Oppenweiler
Telefax +49(0)7191/47-130
Installation instructions V1.8
MICO 2.10 Art.-No.: 9000-41042-0401000
MICO 2.10
Installation instructions
Wiring diagram:
Operating
voltage
+24V DC
Bridging
16 mm² (7)
Bridging ON (6)
Summation message (5)
Module anchorage to
the bridging (9)
Bridging
4 mm² (8)
Earth (GND)
Functional description:
MICO 2.10 is a 2-channel electronic auxiliary circuit switch and serves as current monitoring. The operating
voltage (+24V DC/at least 20A) is split into 2 current monitored load circuits (channels). When engaging the
operating voltage the switched-on channels are time-delay activated (time-delay of each channel = 75 ms) to
avoid overload current. The current selector switches
currents of 4A, 6A, 8A or 10A (see disconnecting characteristic). When exceeding the operating current the
corresponding channel will be disconnected pursuant to the disconnecting characteristic. In the event of
voltage dip or power failure the current operating condition will be saved and reestablished after the recovery
of the supply voltage. The setting of the current range during operation leads to the disconnection of the
channel. It may only be switched on manually. Each channel may be manually connected or disconnected
through the buttons
(2)
. The current operating condition is signalised by the LED
displays). All channels disconnected due to overload may be activated through ON (restart)
In addition, the module is provided with a potential-free message output
message (see summation message). A bridging concept permits the lining-up on a 4-channel MICO module
(maximum operating current 40A) without the installation of a cable system. For this purpose a bridging set is
available as an option (see bridging set).
Bridging set:
The bridging set minimises the efforts of wiring if multiple modules are joined together.
It offers the possibility of bridging the following potentials:
+24V DC
(7)
, GND
(8)
, ON
(6)
and summary message
modules
(9)
. The bridging set is optionally available under:
item no.: 9000-41034-0000001 (packing unit 10 pieces)
item no.: 9000-41034-0000002 (packing unit 1 pieces)
Murrelektronik Intelligent Current Operator
Art.-No. 9000-41042-0401000
Operating
voltage
ON (Restart) (3)
+24V DC
Summation message (4)
Button (On / Off)
with status LED (2)
Current selector
switch (1)
Earth
Controlled
(GND)
Switch outputs
OUT1 - OUT2
(1)
enable an independent setting of the operating
(2)
(4)
to establish a summation
(5)
. A connecting piece is necessary to anchor both
-1-
– (red/green, see
(3)
– see restart.