Installation instructions V2.5
MICO 4.6 Art.-No.: 9000-41034-0100600
Technical data:
Input values:
Input voltage:
+24 V DC (SELV/ PELV)
Residual ripple of power supply
< 5% for one-phase, 2% for three-phase
Range of working voltage
18-30 V DC
Frequency of power ON/OFF max 0,5Hz
Suppressor diode
36 V
No reverse polarity protection
(-10 to +20%)
Total operating current:
24 A
Maximum summation current of +24 V
terminals:
40 A
Output values:
Nominal output voltage:
24V DC, corresponding to the input voltage
Voltage drop at 6A per each load branch:
typical 0,2 V
Turn ON capacity:
max. 20 mF*
Internal fuse: 6,3 A delay fuse for each channel
* Dependent on: component tolerance, conduit length, used power supply, load current, selected current range
Schematic circuit diagram:
24V DC
Message 1-4
GND
Button
Control Logics
Reset
OUT
13
14
Load
Notice:
Please pay attention to the wire capability in relationship of its cross section, ambient temperature, current as
well as the used protection.The in 4 levels settable channel current serves as the wire protection and device
protection conform to EN60204-1, referring to the maximal permissible channel current. For lucid reasons
this installation instructions does not contain detailed information to all types of this product and may not
consider each fictitious case of erection, operation or installation. Continuing information may be taken from
the data sheet or from our homepage in the internet
http://www.murrelektronik.com.
Technical alterations are reserved at any time.
© 2009 Murrelektronik GmbH, Oppenweiler
All rights reserved. Each reprint, even in parts, requires our written consent.
Murrelektronik GmbH
P.O. Box 1165
Falkenstrasse 3
info@murrelektronik.com
Murrelektronik Intelligent Current Operator
Signalling: See "Displays"
Environment:
Storing temperature:
-40° C to +80° C
Environmental temperature: 0 to +55° C
Cooling by natural convection
Safety:
Rated insulation voltage: 50V
degree of pollution: 2
Classification of over-voltage III
Additional output protection:
6,3A fuse for each channel internal
(UL 248-14, UL File E10480).
Regulations:
EN 60529: Protective system - IP20
EN 61000-6-2: Immunity to interference
EN 61000-6-3: Interference emission class B
EN 60068-2-6: Oscillating test
EN 60068-2-27: Shock test
Weight: ca. 160g
Measurements LxWxD: 90x70x80 mm
+24
1
2
3
4
Load
Load
Load
1
2
3
4
D-71567 Oppenweiler
Telefon +49(0)7191/47-0
D-71570 Oppenweiler
Telefax +49(0)7191/47-130
http://www.murrelektronik.com
Installation instructions V2.5
MICO 4.6 Art.-No.: 9000-41034-0100600
MICO 4.6
Art.-No. 9000-41034-0100600
Installation instructions
Wiring diagram:
ON (Restart) (3)
Summation message (4)
Operating
voltage
+24V DC
Button (On / Off)
with status LED (2)
Current selector
switch (1)
Earth (GND)
Controlled
Switch outputs
OUT1 - OUT4
Functional description:
MICO 4.6 is a 4-channel electronic auxiliary circuit switch and serves as current monitoring. The operating
voltage (+24V DC/at least 10A) is split into 4 current monitored load circuits (channels). When engaging the
operating voltage the switched-on channels are time-delay activated (time-delay of each channel = 75 ms) to
avoid overload current. The current selector switches
currents of 1A, 2A, 4A or 6A (see disconnecting characteristic). When exceeding the operating current the
corresponding channel will be disconnected pursuant to the disconnecting characteristic. In the event of
voltage dip or power failure the current operating condition will be saved and reestablished after the recovery
of the supply voltage. The setting of the current range during operation leads to the disconnection of the
channel. It may only be switched on manually. Each channel may be manually connected or disconnected
through the buttons
(2)
. The current operating condition is signalised by the LED
displays). All channels disconnected due to overload may be activated through ON (restart)
In addition, the module is provided with a potential-free message output
message (see summation message). A bridging concept permits the lining-up of multiple modules (maximum
operating current 40A) without wiring. For this purpose a bridging set is available as an option (see bridging
set).
Bridging set:
The bridging set minimises the efforts of wiring if multiple modules are joined together.
It offers the possibility of bridging the following potentials:
(7)
(8)
(6)
+24V DC
, GND
, ON
and summary message
modules
(9)
. The bridging set is optionally available under:
item no.: 9000-41034-0000001 (packing unit 10 pieces)
item no.: 9000-41034-0000002 (packing unit 1 pieces)
Murrelektronik Intelligent Current Operator
Operating
voltage
+24V DC
Bridging
16 mm² (7)
Bridging ON (6)
Summation message (5)
Module anchorage to
the bridging (9)
Bridging
4 mm² (8)
Earth (GND)
(1)
enable an independent setting of the operating
(2)
– (red/green, see
(3)
– see restart.
(4)
to establish a summation
(5)
. A connecting piece is necessary to anchor both
-1-