I
NTRODUCTION
The ATS1230 Wireless Data Gathering Panel (DGP) receiver
expands the Advisor Master panel's input capability by up to 32
™
zones using GE Interlogix
Transmitter Sensors (crystal or SAW).
The ATS1230 may be located up to 335 meters (1100 feet) from
the Advisor Master panel using a WCAT52/54 cable. It receives
information from a range of compatible sensor types programmed
into the DGP.
The ATS1230 features spatial diversity to minimize wireless signal
nulls or dead spots and has a nominal open-air receiving range of
460m. If dead spots need to be eliminated, a 433MHz repeater
may be used. It may be powered from the Advisor Master BUS
power or a remote auxiliary power supply.
Fob buttons may be programmed for users to arm and disarm or to
control relays, for example, to remotely open and close a garage
door as well as arm or disarm an office security system.
The basic component overview is shown in figure
D
ATS1230 (R
ESCRIPTION OF THE
1
Circuit board
2
Antenna terminal Block
3
Loop antenna
4
Device ID number label
5
Status LED
6
Cover tamper
7
Terminal strip
8
Mounting holes
B
S
L
(R
ASIC
YSTEM
AYOUT
The Advisor MASTER panel collects the data from the wireless
DGP on the data bus. It provides the power supply to the DGP or a
remote 220V powered DGP can supply power to the ATS1230.
The ATS1230 receives the RF signal from the wireless devices i.e.
PIR, FOB or Smoke Detector.
A programmable supervisory signal checks the state of the devices
in the field.
M
L
OUNTING
OCATION
The ATS1230 can be mounted on any interior wall.
Leave 16 cm above the wireless DGP plastic enclosure for the
antenna.
IMPORTANT:
Avoid areas likely to expose the wireless DGP to
moisture.
Avoid excessive metal or electrical wiring, e.g. furnace &
utility rooms.
If mounting wireless DGP near metal, give the antenna
as much clearance as possible.
Remove power from the Advisor MASTER panel before
commencing installation.
M
OUNTING THE UNIT
Mounting the ATS1230 DGP (Ref. to fig.
1)
Remove power from the Advisor Master panel.
2)
Remove the ATS1230 plastic cover.
3)
Hold the base of the ATS1230 against the mounting surface
and mark the three mounting holes. (Leave 18 cm of free
space above for the antenna.)
4)
Drill holes and insert screw anchors, if required.
5)
Secure the unit to the mounting surface with screws provided.
If mounted near metal, give the antenna as much clearance
as possible.
6)
If back tamper is required, secure the magnet (supplied)
close to reed switch, just below the address DIPswitches in
the empty area of the back plate. (See PCB diagram). (The
tubular plastic protrusion in the cable entry slot may be cut
away). TIP: Remember to enable the rear tamper in the
ATS1230 menu option 9 - Tamper Options.
Connecting the ATS1230 (Ref. to fig.
™
Learn Mode
433MHz Wireless
.
)
EF TO FIG
.
.
)
EF
TO FIG
)
)
1)
Connect the four BUS cable wires to the terminal strip on the
DGP.
2)
Connect (auxiliary) power supply from the control panel or
DGP to +12V and 0V (J3).
3)
A = D+
4)
B = D-
5)
Connect the BUS cable directly to the Advisor Master panel
BUS and Auxiliary power or use a separate power cable to
the nearest 220V-powered DGP. (In that case 0V needs to be
connected to the panel and the DGP as well).
W
IRING SPECIFICATIONS
Wire Gauge / diameter
(Unshielded or Shielded)
AWG
Mm2
22
0,51
Connecting the antenna to the module
Loosen the inside terminals of the left and right antenna terminal
blocks.
Insert the antenna into the innermost terminals of the antenna
terminal block at the top of the circuit board and tighten the screws
(Insert antenna through cabinet top holes first when module is
mounted inside panel cabinet). The ATS1230 tamper will not reset
unless the antenna is correctly installed.
Addressing the ATS1230 Wireless DGP (Ref. to fig.
Set the ATS1230 address DIPswitch. Each Wireless DGP,
connected to the Advisor Master BUS must identify itself to
the Advisor Master panel with its own address, set with the
DIPswitches on the DGP. The diagram shows the DIPswitch
settings for 15 possible Wireless DGP addresses. Address
0 is a factory test setting — do not use it.
Closing the ATS1230 Wirless DGP housing
1)
Replace the plastic cover. Make sure the cover tamper switch
extension spring is in place on the tamper switch.
2)
Mount sensors and 433MHz Repeater (a Repeater can be
added later if sensor performance or signal strength is found
to be inadequate).
Powering Up the ATS1230 Wirless DGP
Before powering up the panel and receiver module:
1)
Verify that all wiring at the panel and ATS1230 wireless
receiver is correct.
2)
Connect the panel backup battery and AC power.
Verify that the receiver module status LED is on.
P
ROGRAMMING
Refer to the panel installation guide for more details.
T
ESTING
Test the receiver module at the desired location to evaluate
performance in the particular environment.
Verify that the receiver module LED flashes when wireless devices
are activated.
For complete testing procedures, refer to the panel installation
guide.
3
Wireless DGP
Max. Wire length between
module and panel
Feet
Meters
1100
335
)