ccei NIVA3 Notice Technique page 15

Masquer les pouces Voir aussi pour NIVA3:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
Technical instructions
S1
S2
S3
S4
M
NIVA 5 uses 5 level probes. The probes must be positioned in the buffer tank so that
the manual override level (S1) is below the buffer tank overflow.
Warning: To guarantee the reliability of detection, you are advised to install the
probes in a chute or a PVC pipe in order to isolate them from the wall and to
keep them separate. The probes must be fixed at the desired height to prevent
their movement and to avoid any pulling on the wire. The probe wires must be
guided to avoid their becoming tangled.
The probes are supplied with a length of cable which can prove insufficient to
connect
them
regulation box. You are
then advised to prolong
the cables by using a
junction
box.
connection between the
regulation box and the
junction box should not
exceed 50 m and will be
made with a 5-strand
flexible
cable
for
NIVA 5 (or 3 strand
flexible
cable
for
NIVA3) 1.5 mm ² (HO7RNF type for example). To ensure a good performance of
the installation, it is essential to ensure the sealing of the junction box and good
galvanic insulation of the contacts. The use of silicone adhesive is recommended.
To avoid wiring errors, the multi-strand wires must be
clearly marked, particularly if the 5 strands are not of
different colours. For the RO2V for example, care
should be taken to mark the position of the 2 black
wires.
CCEI
Manual override off
End of filling
Start of filling
to
the
The
Chute
the
Goulotte
the
NIVA
Manual override
Junction box
Boîte de
Cable type HO7R NF
dérivation
5
5
Câble type RO2V
SEAL
ETANCHEITE
Sondes écartées les
Probes separated
unes des autres et
from each other and
isolées de la parois
isolated from the walls
par une goulotte.
by a duct. The probe
Les fils des sondes
wires are combed.
sont peignés.
v3.0
Marking of
Repérage
wires
Regulation
Coffret de
des fils
unit
régulation
Yellow/
Jaune/Vert
green
Black 2
Black 1
Noir 1
Noir 2
Blue
Bleu
Marron
Brown
Câble type RO2V
Cable type HO7R NF
Front view
vue de face
page 7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Niva5Pf10l008

Table des Matières