GB
INSTRUCTIONS FOR USE
Non contact voltage indicator with audible warning and self-test feature. For
conductors energised at voltages in the range of 100V to 600V AC.
Hold the voltage sensing device in the palm of the hand. Slide the switch across to
the middle 'TEST' position with the thumb and check that both green and red
indicators are on and that the audible tone is present. Slide the switch to the far
right 'ON' position and check that the green indicator in on. The sensing device is
now ready for use. The red indicator and audible tone will indicate and sound
simultaneously when the nose of the sensing device is placed in the proximity of a
live conductor.
TECHNICAL SPECIFICATION
Battery: 9v alkaline battery, MN1604 or equivalent (not included).
Voltage Range: 100V to 600V AC.
Voltage Sensitivity: See table below.
Frequency Range: 50Hz to 50kHz.
Indicators: LED (red) and audible tone (3kHz) - voltage present. LED (green) -
battery ok.
Operating Temperature Range: -5 to 40°C.
Case Details: Yellow ABS.
Dimensions: 202 x 32 x 22mm.
Weight: 140g (excluding battery).
TYPICAL SENSING DISTANCE OF ENERGISED CABLE
Cable Type:
110V AC 50Hz
Flat 1mm
2
Twin & Earth:
3mm
2.5mm
2
Twin & Earth:
5mm
Round 1.5mm
2
:
2mm
WARNING
The sensing device must be tested before and after use to ensure full
functionality. DO NOT USE THE TESTING DEVICE IF THE RED, GREEN AND
AUDIBLE TONE INDICATORS ARE NOT SIMULTANEOUSLY ACTIVATED IN
THE TEST POSITION. When testing for the presence of voltage in multi-core
cables always run the sensing device along a short length of cable so as to
overcome the natural twist in conductors.
Replace battery if the green light fails to illuminate.
2
240V AC 50Hz
23mm
23mm
18mm
7