Malm Fireplaces, Inc.
368 Yolanda Avenue - Santa Rosa, Ca 95404
Assembly And Installation Instructions
LEAVE THESE INSTRUCTIONS WITH THE OWNER.
Listed Vented Decorative Gas Appliance
Open Windows
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier; call the
fi re department.
WARNING: Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual. For as-
sistance or additional information consult a qualifi ed installer; service agency
or the gas supplier. Do not store or use gasoline or other fl ammable vapors
and liquids in the vicinity of this or any other appliance.
Do not use this appliance if any part has been under water. Immediately call
a qualifi ed service technician to inspect the heater and replace any part of
the control system and any gas control that has been under water.
(707) 523-7755 - Fax: (707) 571-8036
GAS SPIN-A-FIRE
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
ANSI Z21.50
CSA/CGA 2.22-2014

Publicité

loading

Sommaire des Matières pour Malm Fireplace GAS SPIN-A-FIRE

  • Page 1 Malm Fireplaces, Inc. 368 Yolanda Avenue - Santa Rosa, Ca 95404 (707) 523-7755 - Fax: (707) 571-8036 GAS SPIN-A-FIRE ANSI Z21.50 CSA/CGA 2.22-2014 Assembly And Installation Instructions LEAVE THESE INSTRUCTIONS WITH THE OWNER. Listed Vented Decorative Gas Appliance FOR YOUR SAFETY...
  • Page 2 GENERAL INFORMATION This appliance has been tested in accordance with National Safety Standards and has been certifi ed by Warnock Hersey for installation and operation as described in this manual. Please read all the instructions before beginning your installation. Check with your local building code agency to ensure compliance with local codes.
  • Page 3 VENTING The unit is a vented appliance and must be connected to a chimney/fl ue in accordance with the code, using the chimney manufacturer's instructions. Minimum connector length is 4'. This appliance must not be connected to a chimney fl ue servicing a separate solid fuel burning appliance.
  • Page 4 CLEARANCES Make sure that minimum clearances to combustible materials are maintained during installation including adequate space for the proper operation and servicing of the heater. The minimum clearances from the appliance to combustibles are shown on figures 1 and 2. Place the appliance on a flat, solid, continuous surface (i.e.
  • Page 5 Glass Installation Wear eye protection during the assembly of this unit. Check all glass and parts for damage. Replace any damaged parts prior to continuing the installation. Do not assemble this unit with any damaged parts. If you should happen to break a glass panel, it must only be replaced with ceramic glass. 1.
  • Page 6 Installation Instructions Do Not Install In A Mobile Home READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING THE INSTALLATION. 1. Position unit to comply with the minimum clearances to combustible materials. Minimum clear- ances are shown in fi gures 1 and 2. It is recommended that no overhead cross members in the ceiling or roof be cut.
  • Page 7 Chimney Connector Instructions Insulated Pipe 8" Insulated Class "A" Ceiling Chimney System Single Wall Chimney Adapter Slip Connector. Sheet 24" Sheet Metal Screw to Chimney Metal Connector. Screw Slip Connector 24" Automatic Thermal Damper DuraVent 8DBK-ADSL Adapter Spin-A-Fire Includes ICC Excel Flue Extension (8EX) 3 - 8"...
  • Page 8 OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life. A. Follow these instructions exactly. This appliance has a pilot which must be lighted by hand. B.
  • Page 9 MAINTENANCE INSTRUCTIONS GENERAL SAFETY 1. Always shut off the gas supply and make sure that the heater is cool before starting any servicing operation. 2. Always check for leaks after servicing. 3. Always check for correct combustion and ventilation air fl ow. The fl ow of combustion air and ventilation air must not be obstructed.
  • Page 10 ITEM PART NO. DESCRIPTION MV-1 Dexen VALVE 6003 Natural Gas Conversion Kit L.P. Gas MV-1A Valve Control MV-1B Piezo Igniter Button MV-4 High Limit Switch 350 Degree MV-5 Piezo Lighter Wire MV-6 Gas Line In MV-7 Thermopile Wire MV-8 Pilot Supply Tube MV-9 Gas Line to Burner MV-10...
  • Page 11 Valve Wiring Schematic WHITE BLACK DEXEN 6003 GAS VALVE NATURAL GAS 3.5 WC MAX 1/2 PSI FOR MILIVOLT SYSTEM ONLY LP/PROPANE CONVERSION KIT 10 WC To add a remote control or wall switch follow the steps below. 1. Remove the Jumper wire from TH and TP/TH 2.
  • Page 12 Burner Air Shutter Figure F Pilot Flame 1. Place the volcanic rock around the burner. Keep the rock away from the pilot assembly. 2. Arrange the logs around the burner as desired. Move the logs to obtain the desired appearance. WARNING! The logs may become hot when ex- posed to fl...
  • Page 13 Malm Fireplaces, Inc. 368 Yolanda Avenue - Santa Rosa, Ca 95404 (707) 523-7755 - Fax: (707) 571-8036 GAS SPIN-A-FIRE ANSI Z21.50 CSA/CGA 2.22-2014 Assemblage et l'installation Instructions Laisser ces instructions avec le propriétaire. Inscrite ventilé appareil au gaz décoratif POUR VOTRE SÉCURITÉ...
  • Page 14 INFORMATIONS GÉNÉRALES Cet appareil a été testé conformément aux normes de sécurité nationales et a été certifi é par Lab test pour l'installation et le fonctionnement de la manière décrite dans ce manuel. Se il vous plaît lire toutes les instructions avant de commencer votre installation. Vérifi ez auprès de votre agence de code du bâtiment local pour assurer la conformité...
  • Page 15 ÉVACUATION L'appareil est un appareil ventilé et doit être raccordé à une cheminée / fumées conformément à ce code, en utilisant les instructions du fabricant de la cheminée . Longueur de connecteur minimale est de 4 '. L'évent de sortie ne doit pas être encastré dans un mur ou le revêtement. Cet appareil ne doit pas être raccordé...
  • Page 16 DÉGAGEMENTS Assurez-vous que les dégagements minimum aux matériaux combustibles sont maintenus lors de l'installation, y compris un espace suffi sant pour le bon fonctionnement et l'entretien de l'appareil. Les distances minimales de l'appareil aux matériaux combustibles sont indiqués sur les fi gures 1 et 2. Placer l'appareil sur une surface plane solide, continu ( c.-à- bois, tuiles , béton, métal ).
  • Page 17 Installation Verre Porter des lunettes de protection lors de l'assemblage de cet appareil. Vérifi ez tout le verre et les pièces. Remplacer les pièces endommagées avant de poursuivre l'installation . Ne pas monter cette unité avec les pièces endommagées . Si vous devez arriver à briser une vitre , il doit être remplacé avec verre céramique.
  • Page 18 Instructions d'installation Ne pas installer dans une maison mobile LIRE ATTENTIVEMENT TOUTES LES INSTRUCTIONS AVANT DE COMMENCER L'INSTALLATION . Unité de mesure de respecter les distances minimales aux matériaux combus- tibles . Les dégagements minimaux sont indiqués dans les fi gures 1 et 2. Il est recommandé...
  • Page 19 Chimney Connector Instructions Insulated Pipe 8" Insulated Class "A" Ceiling Chimney System Single Wall Chimney Adapter Slip Connector. Sheet 610mm Sheet Metal Screw to Chimney Metal Connector. Screw Slip Connector 610mm Automatic Thermal Damper DuraVent 8DBK-ADSL Adapter Spin-A-Fire Includes ICC Excel Flue Extension (8EX) 3 - 203mm x 610mm Pipe Sections Selkirk Stovepipe Adaptor Or Single Wall Chimney Adapter...
  • Page 20 MODE D'EMPLOI POUR VOTRE SÉCURITÉ LIRE AVANT ECLAIRAGE AVERTISSEMENT : Si vous ne suivez pas ces instructions à la lettre, un incendie ou une explosion entraînant des dommages matériels, des blessures ou des pertes de vie. A. Suivez ces instructions à la lettre. Cet appareil possède une veilleuse qui doit être allumée à la main.
  • Page 21 INSTRUCTIONS DE MAINTENANCE SÉCURITÉ GÉNÉRALE 1. Toujours fermer l'alimentation de gaz et assurez-vous que le chauff e-eau est froide avant de commencer toute opération de maintenance. 2. Toujours vérifi er les fuites après l'entretien. 3. Toujours vérifi er pour la combustion et le débit d'air de ventilation. Le débit de combustion air et air de ventilation ne doivent pas être obstruées.
  • Page 22 ITEM PART NO. DESCRIPTION MV-1 Dexen VALVE 6003 Natural Gas Conversion Kit L.P. Gas MV-1A Valve Control MV-1B Piezo Igniter Button MV-4 High Limit Switch 350 Degree MV-5 Piezo Lighter Wire MV-6 Gas Line In MV-7 Thermopile Wire MV-8 Pilot Supply Tube MV-9 Gas Line to Burner MV-10...
  • Page 23 Câblage Valve schématique OPTION interrupteur mural, Thermostat ou REMOTE LIMITE HAUTE SWITCHTCH UTILISÉ DEXEN 6003 ROBINET DE GAZ GAZ NATUREL 3,5 WC MAX 1/2 PSI POUR UN SYSTÈME DE MILIVOLT SEULEMENT LP/PROPANE CONVERSION KIT 10 WC Pour ajouter une télécommande ou un interrupteur mural, suivez les étapes ci-dessous. 1.
  • Page 24 Burner Air Shutter Figure F Pilot Flame 1. Placez la roche volcanique autour du brûleur. Gardez le rocher loin de l'assemblage de la veil- leuse. 2. Disposez les journaux à travers le brûleur dé- siré. Déplacez les journaux pour obtenir l'apparence souhaitée.