Coffret SAV Micro 3000
Notice d'installation, d'utilisation et d'entretien
14.4 Paramètres de communication esclave Modbus
MODBUS
Speed / Vitesse :
PARAMETERS
Bit number / Nbre de bits :*
/
Stop bit / Bit de stop :
PARAMETRES
Parity / Parité :
MODBUS :
Mode :
ModBus Points
Points ModBus
(English)
(Français)
PD_Cmd_P1
PD_Cmd_P1
PD_Cmd_P2
PD_Cmd_P2
PD_Cmd_P3
PD_Cmd_P3
PD_Cmd_P4
PD_Cmd_P4
PriP1_Alarm_On
PriP1_Alarme_Ma
PriP2_Alarm_On
PriP2_Alarme_Ma
SecP3_Alarm_On
SecP3_Alarme_Ma
SecP4_Alarm_On
SecP4_Alarme_Ma
PD_High_Alarm
PD_Alarme_Hte
PD_Main_Alarm
PD_Alarme_Synt
Fooling_Alarm
Alarme_Encrasst
ThermTr_Alarm
Alarme_TrTh
PD_Triac_Output
PD_Sortie_Triac
SAFETY_FCT
FCT_SECOURS
AFF_Leg_active
AFF_TrTh_actif
Remote_Control_Rev Contrl_Distant_Inv
AFF_FD20
AFF_FD20
AFF_FD22
AFF_FD22
BOOSTER
BOOSTER
ECO
ECO
PD_Pumps_Fault
PD_Defaut_pompes
Tank_load
Charge ballon
SW AL Version
SW AL Version
PA10_valve1
PA10_Vanne1
S1_10
S1_10
S2_10
S2_10
S3_10
S3_10
S1_PID_SP_10
PC_S1_PID_10
High_Alm_Reset
Reset_Alm_Hte
Pump fault Reset
Reset_Def_Ppes
SP_T_Sec_Outlet
Consigne_S1
ThTr_setpoint
PC_TrTh
*
For some supervisors, it is necessary to implement BOOL as int16
** For some supervisors, remove 1 to adress number (ex : S1_10 adress=49) ** Sur certains superviseurs, enlever 1 au numéro du point modbus (ex: S1_10 à l'adresse 49)
*** If present
9600
In case of multiple controllers, change ModBus slave number
En cas d'echangeur en cascade changer le N° d' esclave du mode bus
8
1
None / Aucune
RTU
MODBUS adress**
Type
Sub-type
Adresse ModBus**
Sous-type
Read Only digital / Lecture seule Digitaux
15
HR _16
BOOL
16
HR _16
BOOL
17
HR _16
BOOL
18
HR _16
BOOL
19
HR _16
BOOL
20
HR _16
BOOL
23
HR _16
BOOL
24
HR _16
BOOL
27
HR_16
BOOL
28
HR_16
BOOL
30
HR_16
BOOL
32
HR_16
BOOL
33
HR _16
BOOL
35
HR_16
BOOL
36
HR_16
BOOL
37
HR_16
BOOL
39
HR_16
BOOL
40
HR_16
BOOL
41
HR_16
BOOL
42
HR_16
BOOL
43
HR_16
BOOL
44
HR_16
BOOL
(16 bit integer/Entier 16 bit)*
Read Only Analogic / Lecture seule Analogiques
34
HR_16
47
HR_16
50
HR_16
51
HR_16
52
HR_16
62
HR_16
(16 bit integer/Entier 16 bit)*
Read-Write digital / Lecture-Ecriture Digitaux
201
HR_16
BOOL
202
HR_16
BOOL
(16 bit integer/Entier 16 bit)*
Read-Write Analogic / Lecture-Ecriture Analogiques
211
HR_16
213
HR_16
(16 bit integer/Entier 16 bit)*
* Sur certains superviseurs, renseigner les digitaux comme entiers 16 bit
*** Si présente
Mode
Value
Valeur
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=OK, 1=Alarm
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
R
0=Off, 1=On
int16
R
int16
R
%
int16
R
°C
int16
R
°C
int16
R
°C
int16
R
°C
R/W
1=Reset fault. Pulse point necessary 30 seconds On/Off
R/W
1=Acquittement. Point impulsionnel On/Off pendant 30 secondes
int16
R/W
°C
int16
R/W
°C
38
Comment
Commentaire
Command(e) P1
Command(e) P2
Command(e) P3
Command(e) P4
P1 Fault / Défaut P1
P2 Fault / Défaut P2
P3 Fault / Défaut P3
P4 Fault / Défaut P4
S1 High Temp Alarm/Alarme haute S1
General default / Défaut synthèse
Fooling alarm (S3) / Alarme encrassement (S3)
Therm.Treat. Failed / Echec traitement therm.
230V Triac output / Sortie triac 230V
Safety function / Fonction Secours
Therm.Treat. On going / Trait. Therm. En cours
Remote control / Contrôle distant
Heating mode / Mode chauffage
Cooling mode / Mode froid
BOOSTER active
ECO activated
Synthesis pump(s) fault / Défaut synthèse pompe(s)
Tank loaded / Ballon chargé
Software version / Version logiciel
Control vlave 1 signal / Signal servomoteur 1
Sensor 1 measurement / Mesure Sonde S1
Sensor 2 measurement / Mesure Sonde S2
Sensor 3 measurement / Mesure Sonde S3
Calculated S1 setpoint / Pt de consigne calculé S1
S1 fixed setpoint (DHW) / Consigne fixe S1 (ECS)
Thermal treatment setpoint / Consigne trait. thermique