ROUTINE MAINTENANCE INSTRUCTIONS
The.following.maintenance.procedures.will.extend.the.service.life.of.this.appliance .
WARNING:.
Maintenance.should.not.be.performed.while.flowing.water . . Disconnect.from.water.supply.prior.to.
maintenance .
A . . Piston.Rod.Lubrication.-.Lightly.grease.each.end.of.the.piston.rod.with.Parker-O-Lube.or.equivalent.barium.grease.when.it.
becomes.dry.or.every.three.(3).months . . When.greased.properly,.the.rod.will.have.an.evenly.dispersed.layer.of.grease.covering.
the.exposed.portion.of.the.rod . . Distribute.grease.evenly.by.pushing.the.outlet.back.and.forth .
B . . Safety.Straps.-.Examine.strap.for.wear.and.make.sure.both.hooks.easily.snap.into.the.front.leg.clips . . If.straps.need.
replacement,.contact.your.local.Akron.Brass.Distributor .
C . . Every.six.months,.lightly.grease.the.threaded.portion.of.the.elevation.brake.knob.with.Parker-O-Lube.or.equivalent..
barium.grease .
D . . . Examine.the.points.of.the.ground.spikes.in.the.portable.base . . If.the.flat.of.any.spike.exceeds.
sharpened.or.replaced . . To.sharpen,.use.a.flat.file.or.grinder.and.maintain.the.same.taper.as.the.original.spikes . . If.a.grinder.is.
used,.do.not.allow.the.spikes.to.become.hot,.or.change.color,.since.this.will.reduce.the.hardness.and.will.not.remain.sharp..
in.service .
E . . . Check.the.spring.loaded.spike.holders.in.the.portable.base.to.ensure.that.they.move.freely . . Use.a.dry.spray.lubricant.if.
lubrication.is.required .
F . . . Check.that.the.elevation.safety.stop.operates.properly . . This.stop.must.be.released.to.lower.the.unit.below.45˚.elevation .
G . . . Check.both.the.inlet.clappers.function.properly.on.the.Dual.Inlet.Base . . Lubrication.is.not.normally.required.in.this.area .
H . . . Check.that.the.latch.of.the.safety.chain.hook.engages.properly.in.the.chain .
I . . . If.any.of.the.parts.do.not.function.properly,.contact.Akron.Brass.for.repair.instructions.or.return.the.unit.to.either.Akron.Brass.
Company.or.Akron.Manufacturing.Company .
TROUBLESHOOTING
If.the.unit.fails.to.operate.properly.or.stops:
A . . Check.oscillation.ON/OFF.knob . . Make.sure.knob.is.pulled.out .
B . . Check.operating.pressure . . Make.certain.an.operating.pressure.of.at.least.70.PSI.(438.kpa,.4 . 8 3.bar).is.maintained .
C . . Check.travel.control.knobs . . Do.not.place.both.travel.control.knobs.on.the.center.position.at.the.same.time . . If.you.want.to.
stop.the.oscillation,.depress.the.oscillation.ON/OFF.knob.as.previously.described.in.the.Operating.Instructions,.Section.C .
D . . If.the.unit.stops.during.operation,.lower.the.line.pressure.to.zero,.push.the.discharge.outlet.against.the.left.stop..
and.repressurize .