INSTRUCTION
EN
SE25M24
i
Read this instruction before installation
and wiring of the product
Valve actuator for 0(2)...10 V control
RVAN25-24A is a valve actuator designed for control of AB Industriet-
echnik valves. The actuator has automatic self stroke adjustment and
can be operated manually.
Technical data
Supply voltage
24 V AC ±15 %, 50/60 Hz
or 24 V DC ±15 %
Control signal
0(2)...10 V DC
Power consumption
Max. 12 W
Stroke
10...52 mm
Stroke time
3 s/mm
Force
2500 N
Ambient temperature
0...50°C
Storage temperature
-40...80°C
Ambient humidity
10...90 % RH
Dimensions (WxHxD)
198 x 309 x 133 mm
Protection class
IP54
Installation
If the valve stem lock and valve throat adaptor are not already mounted
on the valve, mount them. Pull the valve stem out as far as possible.
Remove the screws (hex key 6 mm) and clamp from the actuator yoke.
Depress the spring-loaded tab on the drive rod coupling device and fit the
valve stem into the coupling.
Release the tab to connect the valve to the actuator. The position of the
yoke on the valve stem adaptor must be adjusted so that the clamp screw
holes line up with the groove in the valve throat adaptor. If the drive rod
needs to be moved in or out for this, depress the central button of the
control knob and turn it clockwise to extend the drive rod and counterclock-
wise to retract it (see Manual override). Mount the screws and the
clamp. Tighten the screws until the actuator is firmly attached.
Disassembly takes place in reverse order.
Mounting positions
90º
Wiring
U
5
Measuring voltage
for position indication
U 0...10 V DC
Signal neutral
Y 0(2)...10 V DC
Control signal from
controller
Stroke and endpoint calibration
Stroke and endpoint calibration is not necessary due to a construction
utilizing endpoint stops. When the valve reaches the endpoint, a force is
generated. Once the force of the actuator reaches a predefined level, the
limit switch automatically halts the drive motor.
SE25M24
Override
Activation of the override input will force the valve to the maximum
open position.
Manual override
90º
To manually set the valve position, first depress the central part of the
knob, until it clicks and remains depressed (1 in the figure). Then the
valve position can be changed manually by turning the knob (2 in the
figure). When the knob is turned clockwise, the drive rod is pushed
outwards and when the knob is turned anti-clockwise, the drive rod is
pulled inwards.
To return to normal operation, set the knob so that it is in line with the
text "Auto" on the cover. Then depress the outer parts of the knob (3
in the figure). The central depressed part will pop out, and the actua-
tor will return to normal operation.
G0
G
B
M
Y
Note: After any manual operation the actuator will always run through
4
3
2
1
6
a zero point calibration.
DIP switches
There are five DIP switches for setting different functions. Follow the
table below for setting the DIP switches.
Adjusted settings will be valid only after the next power-on.
SW1
SW2
SW3
24 V AC/DC
SW4
SW5
SW1 Operational direction of the valve
On: The valve is closed when the stem is in its lowest position.
1 (On)
0 (Off)
Spindle down when the
Spindle up when the valve is
valve is closed
closed (FS=factory setting)
Y = 2...10 V DC
Y = 0...10 V DC (FS)
Reverse operation
Direct operation (FS)
Y signal split in accordance
No split function (FS)
with the setting of SW5
5(6)...10 V = 0...100 %
0(2)...5(6) V = 0...100 % (FS)
1

Publicité

loading

Sommaire des Matières pour Industrie Technik SE25M24

  • Page 1 INSTRUCTION Installation Override SE25M24 If the valve stem lock and valve throat adaptor are not already mounted Activation of the override input will force the valve to the maximum on the valve, mount them. Pull the valve stem out as far as possible.
  • Page 2 SW2 should be set to position On (2...10 V DC). The control signal will then be converted to 2...10 V DC. RoHS Il modello SE25M24 è un attuatore valvola concepito per il controllo SW3 Reverse/Direct operation This product conforms with the Directive 2011/65/EU of the European di valvole AB Industrietechnik.
  • Page 3 Segnale Y suddiviso Nessuna funzione di secondo impostazione di suddivisione (FS) Da 5(6) a 10 V = Dallo 0 al Da 0(2) a 5(6) V = Dallo 0 al 100 % 100 % (FS) SE25M24...
  • Page 4 Moteur de vanne pour contrôle 0(2)...10 V lentamente il funzionamento. La nuova impostazione verrà convalidata al L’actionneur SE25M24 est prévu pour le pilotage de vannes AB Industri- prossimo avvio. etechnik. L’ajustement de la course est automatique. Le moteur dispose Luce fissa verde e rossa Posizione estrema raggiunta.
  • Page 5 Split signal Y selon le rég- Pas de fonction de split (RU) lentement lage de SW5 Voyant rouge fixe Erreur de fonctionnement (montage 5(6)...10 V = 0...100 % 0(2)...5(6) V = 0...100 % (RU) incorrect ou étalonnage de course perdu). SE25M24...
  • Page 6 90º Diese Anleitung vor Montage und Anschluss des Produktes bitte durchlesen Ventilstellantrieb für 0(2)...10 V-Ansteuerung SE25M24 ist ein Stellantrieb für die Ansteuerung von AB Industriet- Anschluss echnik Ventilen. Der Stellantrieb ist mit automatischer Hubanpassung und Handbedienung ausgestattet. Die Ventilstellung kann manuell eingestellt werden, indem der mittlere Teil des Drehknopfes heruntergedrückt wird, bis er einrastet (1 in der...
  • Page 7 Stetiges rotes Licht Fehlfunktion; entweder inkorrekte Installation oder fehlender Hubweg Endlagenanzeige: An der Konsole des Stellantriebs befinden sich eine rote und eine blaue Endlagenmarkierung. Diese Markierungen können einfach verschoben werden, um anzuzeigen, wann das Ventil zum Heizen/ Kühlen offen/geschlossen ist. SE25M24...