TMCX Terminator™ II cable gland
Installation & maintenance information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
TMCX Terminator
II cable fittings are designed for use with Type MC/MC-HL jacketed metal-clad cable, interlocked armor and
continuous corrugated armor, TECK, ITC and Type TC/TC-ER/TC-ER-HL tray cable in hazardous (classified) locations when installed,
in accordance with NEC/CEC. TMCX Terminator II cable fittings are cULus Listed for hazardous locations (with TSC epoxy sealing
compound and Chico
LiquidSeal only) according to UL standards 514B and 2225, and CSA standard C22.2 No. 174. They are suitable
®
for use in NEC/CEC Class I, Divisions 1 & 2, Groups A, B, C, D; Class II, Divisions 1 & 2, Groups E, F, G; and Class III, when installed
in accordance with NEC/CEC, and using appropriately approved cable.
Explosionproof cable fittings should be installed, inspected and maintained by qualified and competent personnel.
WARNING
To avoid risk of electrical shock, electrical power must be OFF
before and during installation and maintenance.
Sealing chamber
Thread body
RECOMENDATIONS FOR INSTALLATION
For all versions, suitable grease must be used on the thread
body, union nut and back nut. Suitable grease must be
non-setting, non-metallic, non-combustible and maintaining
earthing. It can be Eaton's Crouse-Hinds series type HTL or STL
lubricants.
CABLE PREPARATION
1. Remove jacket (and armor, if applicable) from the cable to
expose a sufficient length of conductors required for the job.
When using Type MC cable, leave a length of armor exposed
as specified in the table below.
CABLE JACKET REMOVAL TABLE
When cable O.D. is in
When cable O.D. is in
Cat. #
the top half of the
the bottom half of the
cable range
cable range
TMCX050 0
0.77" (19.56mm)
0.67" (17.02mm)
TMCX075 0
TMCX050 1, 2
TMCX075 1, 2
0.92" (23.3mm)
0.82" (21.0mm)
TMCX100 0, 1, 2
TMCX125 1
Prepare cable. For Type
MC, remove all fillers and
shielding back to armor.
For Type TC, remove
fillers back to cable jacket.
Separate uninsulated ground
conductors back to armor or
sheath to allow sealing of
individual strands.
2. Install TMCX into hub,
wrench-tight.
3. Apply electrical tape to tip of conductors, and slide through
integral dam until armor or TC jacket contacts the dam.
IF 1647 • 03/19
Copyright © 2019, Eaton's Crouse-Hinds Division
Back nut
Environmental seal
Dam
Rear assembly
Union nut
4. Tighten back nut wrench-tight and visually inspect that
environmental seal has collapsed 360° around cable jacket. If
desired, use included torque table as a guideline.
CAUTION
To avoid risk of ignition:
1. Tools must not be allowed to damage the tapered flame
path surfaces. Do not handle sealing chambers roughly,
or use tools that might damage or scratch the tapered
surfaces.
2. Any excess sealing compound should be removed from
the exterior tapered surface of the sealing chamber
immediately.
3. The sealing chamber should be fully bottomed to the rear
assembly before assembly to the thread body.
4. Before reassembly, examine the tapered joint surfaces of
the thread body and sealing chamber. Surfaces must seat
fully against each other to provide a proper explosionproof
joint. Remove any dirt or other foreign matter from both
surfaces. If either surface is scratched, marred, corroded
or otherwise damaged, do not reassemble. Replace the
fitting.
5. After packing sealing chamber with TSC, be sure to allow
compound to harden before moving conductors.
5. Disassemble union nut and remove rear assembly from thread
body.
IF 1647
5a. For Chico LiquidSeal installation: remove electrical tape and
separate conductors. Mix liquid compound per included
instructions. Hold cable gland upright and pour liquid compound
until it reaches the top of the compound chamber. Wiggle and
separate conductors to make sure compound settles between
conductors; use a hardwood stick or dowel if needed to work
around larger cable bundles. Top off if necessary. Maintain
assembly in vertical position until compound has gelled. See
cure graph for gel and energizing times. Minimum storage
temperature for LSC is -60°C.
5b. For Chico LiquidSeal installation with dispenser cartridge: follow
mixing instructions included with the cartridge, then follow the
pouring instructions from 5a.
5c. For TSC installation: (with cables containing more than
four (4) conductors, Chico LiquidSeal is recommended):
unscrew and remove sealing chamber, remove electrical tape
and separate conductors. Mix two-part epoxy sealing compound
provided by kneading and folding until a uniform color is
obtained (approximately 2-3 minutes). Pack a sufficient amount
of compound between and around conductors, using the
length and I.D. of the sealing chamber as a guide for shaping
the compound. Insert conductors into sealing chamber and
slide the sealing chamber down over the sealing compound.
As compound is getting compressed, use a hardwood stick
or dowel to remove excess compound and prevent it from
getting into the mating threads. Screw sealing chamber into
mating thread and pack more sealing compound from the top
of the sealing chamber, making sure conductors are properly
sealed around, and the sealing chamber is completely full.
Wipe off any compound from the sealing chamber's exterior
immediately. Allow compound to sufficiently harden before
moving conductors to avoid creating voids. Allow TSC to cure
for 24 hours before energizing equipment. Minimum storage
temperature for TSC is 40°F (4.4°C).
Entry
NPT
Entry thread
thread
cat. #
(metric option)
1/2"
TMCX050 0
M20
1/2"
TMCX050 1
M20
1/2"
TMCX050 2
M20
3/4"
TMCX075 0
M25
3/4"
TMCX075 1
M25
3/4"
TMCX075 2
M25
1"
TMCX100 0
M32
1"
TMCX100 1
M32
1"
TMCX100 2
M32
1-1/4"
TMCX125 1
M40
*All dimensions in inches; metric millimeters shown in parenthesis.
†When making your cable gland selection based on cable O.D., be sure to also observe the over conductors O.D. dimension.
‡Min. cable O.D. for CSA certification is 0.49 (12.45) for TMCX050 0/TMCX075 0, and 0.57 (14.48) for TMCX100 0.
See pages 7 and 8 for gel time and energize / return to service time graphs.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be
reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and
Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product
for his intended use and assumes all risk and liability whatsoever in connection therewith.
Page 1
6. Insert the rear assembly into the thread body. Tighten
union nut wrench-tight. Assembly is complete.
Cat. #
TMCX050 0
TMCX075 0
TMCX050 1, 2
TMCX075 1, 2
TMCX100 0
TMCX100 1, 2
TMCX125 1
SELECTION TABLE
Over
Armor O.D.
Metric
conductors
cat. #
O.D. max.
Min.
Max.
Min.
inches†
TMCXM20 0
0.480
0.36 (9.14)
0.66 (16.76)
0.45 (11.43)‡
TMCXM20 1
0.480
0.40 (10.16)
0.86 (21.84)
0.49 (12.45)
TMCXM20 2
0.480
0.56 (14.22)
1.14 (28.96)
0.65 (16.51)
TMCXM25 0
0.673
0.36 (9.14)
0.66 (16.76)
0.45 (11.43)‡
TMCXM25 1
0.713
0.40 (10.16)
0.86 (21.84)
0.49 (12.45)
TMCXM25 2
0.713
0.56 (14.22)
1.14 (28.96)
0.65 (16.51)
TMCXM32 0
0.713
0.40 (10.16)
0.86 (21.84)
0.49 (12.45)‡
TMCXM32 1
0.939
0.56 (14.22)
1.14 (28.96)
0.65 (16.51)
TMCXM32 2
0.939
0.78 (19.81)
1.35 (34.29)
0.87 (22.10)
TMCXM40 1
1.172
0.78 (19.81)
1.35 (34.29)
0.87 (22.10)
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, New York 13208 • USA
Copyright © 2019
TORQUE TABLE
Torque in.-lb. (N-m)
700 (79)
800 (90)
1000 (113)
Cable O.D.
Empty sealing chamber
volume [mL]
(assuming no
Max.
conductors present)
0.70 (17.78)
5
0.90 (22.86)
5
1.18 (29.97)
5
0.70 (17.78)
10
0.90 (22.86)
10
1.18 (29.97)
10
0.90 (22.86)
10
1.18 (29.97)
17
1.39 (35.31)
17
1.39 (35.31)
27
IF 1647
Revision 7
Revised 03/19
Supercedes 08/15

Publicité

loading

Sommaire des Matières pour Eaton TMCX Terminator II

  • Page 1 6. Insert the rear assembly into the thread body. Tighten around larger cable bundles. Top off if necessary. Maintain in accordance with NEC/CEC. TMCX Terminator II cable fittings are cULus Listed for hazardous locations (with TSC epoxy sealing union nut wrench-tight. Assembly is complete.
  • Page 2 Eaton’s Crouse-Hinds Division Revision 7 1201 Wolf Street Syracuse, New York 13208 • USA Revised 03/19 IF 1647 • 03/19 © 2019, Eaton’s Crouse-Hinds Division, Tous droits réservés. Page 3 Copyright © 2019 Supercedes 08/15...
  • Page 3 Vea las páginas 7 y 8 para el tiempo de gel y energizar / retorno a los gráficos de tiempo de servicio. IF 1647 • 03/19 Copyright © 2019, Eaton’s Crouse-Hinds Division Page 5 IF 1647 • 03/19 Copyright © 2019, Eaton’s Crouse-Hinds Division...
  • Page 4 IF 1647 Eaton’s Crouse-Hinds Division Revision 7 1201 Wolf Street Syracuse, New York 13208 • USA Revised 03/19 Copyright © 2019 Supercedes 08/15 IF 1647 • 03/19 Copyright © 2019, Eaton’s Crouse-Hinds Division Page 7...