Power LED lights red*
(see explanation below)
= when the 'power' LED lights red, it is possible to request the concerning
*
error by means of pushing the 'power/mode' button shortly. With the 4 LED's
from 'setting' can be read which error is ascertained (LEDs are flashing). See
overview on page 53. Advise also the explanations of the concerning section
of the chapter 'Features'.
Connection problem:
- No battery present
- Bad connection between
battery and charger
- Reverse polarity
- Short circuit
Charger is in a thermal
stop.
AC input too low.
The bulk stage takes longer
than 14 hours.
Hardware/software
problem.
Warning for a too low
battery voltage.
Battery voltage too high.
Charge process stopped.
Temperature sensor error:
- Presence of temp. sensor
does not match with the
setting.
-
No or incorrect tempe-
rature measurements
Check the connection to the
battery on faults.
The charging process will
continue when the charger has
cooled down.
Check the mains voltage. It
should be ≥180VAC.
The battery is damaged/
broken. Check the battery.
Heavy users present during
charge process. Shut down as
many users as possible.
The charger has insufficient
current for the concerning
battery capacity.
Send the charger back to
supplier/manufacturer.
Indication will light for 3 min.
The charge process will start
as usual.
Check if the system voltage is
the same as the output voltage
of the charger
-
Check the charger to
determine whether the
charger has or has not
been set for use of the
temperature sensor.
- Check the connections and
environment.
E N
24