Operation
Rated supply voltage
Rated consumption
Rated supply current
Current circuit consumption
Rated frequency
Nr. max. of capacitors banks controlled
Output relays
Max current on relays common circuit
Switching steps delay
Alarm delay
Power Factor setting
Electrical connections
Mechanical dimensions
Cut out dimension
Plastic case
Cut out dimension
Weight
Mechanical fixing
Protection degree (CEI-EN 605.29)
Working temperature
Storage temperature
Relative humidity
Type service
Read the instructions in this handbook because they provide important indications about the safety of installation, use and
maintenance of installation. Take carefully this handbook for any information.
Check the integrity of the equipment after unpacking it. In case of doubt, don't use the P.F.Corrector and ask for skilled staff.
Note: If the equipment has fallen or has been violently or shaken during shipping, it could suffer internal damage which
may be dangerous.
Before connect the equipment, check the data card: this has to be in conformity with the power electric network (the plate is located
on the back of the P.F. Regulator).
This equipment will be assigned only to the use for which it has been specifically made. Each other use has to be considered
improper and therefore dangerous.
In order for the correct functioning of the equipment the limits of voltage, current and temperature, imposed by the CEI and IEC
standards, must never be exceeded.
The equipment has to be protected from atmospheric conditions. No type of tampering is permitted on the electronic circuits of P.F.
Regulator.
Possible interventions will be performed by COMAR staff.
Comar Condensatori S.p.A. guarantees its own products for twelve months from purchase date. The warranty covers the faults of
materials and manufacture and it has to be understand for goods ex-works. Before the equipment works, all instructions, present on this
handbook, have to be meticulously followed. Breakdowns caused from improper use and/or not conformy to enclosed instructions and
faults caused from tampering by unqualified technicians aren't covered.
The not respect also of a one of the previous points make to decady the right of warranty.
Comar Condensatori S.p.A. are not liable for direct or indirect damages consequent the missing or the incorrect operation.
In any case and for any reason COMAR Condensatori S.p.A. can not be considered liable for possible direct or indirect damages,
consequent the malfunctioning of P.F.Corrector, caused from mistakes of assembly or from inadequate use of the same.
The manufacturer reserves the right to modify data and sizes without previous notice.

6. TECHNICAL DATA

AUTOMATIC or MANUAL
Multivoltage 220÷240/ 380÷415 Vac ±10% (254/440Vac on request)
230/ 400Vac -10% / +5% continuous operation
10 VA
By C.T. secondary winding 5Amps max., 1
2VA
50Hz and 60Hz
3 (series QR3) - 4 (series QR4) - 6 (series QR6)
5Amps 250Vac resistive loads
5Amps at 40°C resistive load
30" first bank - 15" other (7" first bank - 4" other on request)
1"± 1" (only series QR4 and QR6)
0,90 IND ÷ 1,00 IND
With male faston 6,35x0,8 mm.
96x96 mm FRONT panel according to DIN43700 - 102 mm. thickness
91x91 mm. (tolerance -0mm. / +1mm.)
Insulating self-extinguishing material
91x91 mm. (tolerance -0mm. /+ 1mm.)
0,8 Kg
by special accessoires included
IP 40 front panel - IP00 rear side
-5°C / + 50°C
-10°C / + 50°C
max. 90% at 20°C non-condensing
Indoor service, no dusty condition. Do not place directly under sunlight.
GENERAL INSTRUCTION
WARRANTY
LIABILITY
10
st
class - 5VA (Imin. = 500mAmps)
MU 03.04.MMM REV.2